For FUY71/100/125FJ
3.6
Removal of Drain Pump
Procedure
Step
Procedure
1.
Drain pump is located at
piping side.
Cut clamp material of hose,
and disconnect hose from
pump.
2.
Remove four screws to
dismount drain pump.
3.
Dismount drain pump by
pulling it down.
4.
Removing float switch
a.Loosen three mounting
screws to remove drain
pump mounting base.
b.Remove two screws
located at opposite side of
drain pump mounting base
to dismount float switch.
160
Warning
Be sure to turn off all power supplies before disassembling work.
Points
Caution
∗When reconnect drain hose with the
pump, secure hose at joint using
clamping material such as Tielap.
(Clamping material should be normally
included in the stock items.)
Removal Procedure
Si-71A