Si-71A
M1C
Compressor
J1HC
Crank Case Heater
S1PH
Pressure Switch for Maintaining
High Pressure
S1LP
Pressure Switch for Low
Pressure Control
K1M
Magnetic Switch
F1C
Overcurrent Relay
M1F
Outdoor Unit Fan (Upper)
M2F
Outdoor Unit Fan (Lower)
Q1L
Outdoor Unit Fan Motor Safety
Q2L
Thermostat
C1R
Capacitor for M1F
C2R
Capacitor for M2F
A1P
Outdoor Unit Control PC Board∗ EC9528 (EC9538)
A2P
Outdoor Control PC Board
(Models for the FJ Type Only)
R1T
Thermistor (for Outdoor Air)
R2T
Thermistor (for Heat Exchanger) ST8604A
R3T
Thermistor (for Discharge Pipe) ST8606
T1R
Transformer
Y1E
Electronic Expansion Valve
K1S
Starting Relay
C3R,
M1C Capacitor
C4R
C5R
Starting Capacitor
∗ Figures inside parentheses are for E unit (anti-corrosion specifications).
Explanation of Function Operation
R125KY1(E)
JT150BC-YE
33W
ACB-DB82
+0
OFF : 30
(kg/cm²G)
-1
ON : 22±1.5 (kg/cm²G)
20PS-1164-1
OFF : –23±15 (cmHg)
ON : 0.5±0.3 (kg/cm²G)
HOE-20F-TRA1
13A
95W
65W
OFF : 135±5°C
ON : Below 120°C
6µF
6µF
ST9303
TR21H16R2
EKV26D35
EKV-MOZS107B0 (Coil)
R140KY1
JT150BC-YE
15A
100W
EC9640
EKV30D36
Electric Function Parts
R140KTAL
JT150BC-YE
HOE-35F-TRA1
28A
TR21M16R2
59