Procedure of Self-Diagnosis by Remote Controller
4.4

Remote Controller Display Malfunction Code and Contents

Malfunction Code
A1
Failure of PC board ass'y for indoor unit
A3
Malfunction of water level system
A6
Indoor unit fan motor overload / overcurrent / lock
A7
Swing flap motor lock
AJ
Failure of capacity setting
C4
Malfunction of heat exchanger temperature sensor
system
C9
Malfunction of suction air temperature sensor system
E0
Actuation of safety device (outdoor unit)
E1
Failure of outdoor unit PC board ass'y
E3
High pressure malfunction (outdoor unit)
E4
Low pressure malfunction (outdoor unit)
E9
Malfunction of electronic expansion valve (outdoor unit)
F3
Discharge pipe temperature malfunction (outdoor unit)
H3
Failure of high pressure switch (outdoor unit)
H4
Failure of low pressure switch (outdoor unit)
H9
Malfunction of outdoor air temperature sensor system
(outdoor unit)
H9
Malfunction of outdoor air temperature sensor system
(outdoor unit)
J3
Malfunction of discharge pipe temperature sensor
system (outdoor unit)
J5
Malfunction of suction pipe temperature sensor system
(outdoor unit)
J6
Malfunction of heat exchanger temperature sensor
system (outdoor unit)
J6
Malfunction of heat exchanger temperature sensor
system (outdoor unit)
PJ
Failure of capacity setting (outdoor unit)
U0
Malfunction of suction pipe temperature
U1
Reverse phase
U4
Failure of transmission (between indoor and outdoor
unit)
U5
Failure of transmission (between indoor unit and
remote controller)
U8
Failure of transmission (between "main" and "sub"
remote controller
UA
Failure of field setting
UC
Address duplication of central remote controller
„ In the case of the shaded error codes, "inspection" is not displayed. The system operates, but be sure to
Note 1:
Operation when a malfunction occurs may differ according to the model.
96
Contents/Processing
inspect and repair it.
Remarks
Only Air flow dilection adjustment cannot be set.
Either capacity data is set incorrectly, or capacity has
not been set for the data IC
(Note 1)
(Note 1)
(Note 1)
(Note 1)
Either capacity data is set incorrectly, or capacity has
not been set for the data IC
Switch R.S.T. of the 3-phase power supply.
Transmission between indoor and outdoor unit is not
being correctly carried out.
Transmission between indoor and remote controller is
not being correctly carried out.
Transmission between "main" and "sub" remote
controller is not being correctly carried out.
System setting mistake for Twin system.
Si-71A
Troubleshooting