Daikin FF-C Technical Manual

Daikin FF-C Technical Manual

Split unit air conditioner

Advertisement

R22
TECHNICAL MANUAL
Split Unit Air Conditioner
Ceiling Cassette C & E Series
FF-C, FHC-E, FFY-C, FHYC-E
— Cooling only & Heatpump [50Hz] —

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FF-C and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin FF-C

  • Page 1 TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E — Cooling only & Heatpump [50Hz] —...
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Nomenclature........................1 Indoor ..........................1 Outdoor ..........................1 Product Line-Up ......................2 Application Information .....................4 Operating Range ......................4 Refrigerant Circuit Diagrams (C Series) ................5 Refrigerant Circuit Diagrams (E Series) ................7 Installation Guideline ....................11 Sound Data ........................16 Sound Pressure Level ....................16 NC Curve ........................17 Engineering &...
  • Page 4: Nomenclature

    Nomenclature Nomenclature Indoor FF(Y) 10 C X V1 Power Supply V1: 1 phase 50 Hz 220-240V Production X: OYLM Product Series C: C Series E: E Series Capacity 10: 10000 Btu/hr Model Ceiling Cassette 2"x2" (Cooling Only) FHC: Ceiling Cassette 3"x3" (Cooling Only) FFY: Ceiling Cassette 2"x2"...
  • Page 5: Product Line-Up

    Nomenclature Product Line-Up Indoor Unit FF(Y)/FH(Y)C Classifi cation Nomenclature FF10CXV1 FF15CXV1 FF20CXV1 FHC20EXV1 FHC25EXV1 FHC28EXV1 FHC40EXV1 FHC50EXV1 FFY10CXV1 FFY15CXV1 FFY20CXV1 FHYC20EXV1 FHYC25EXV1 FHYC28EXV1 FHYC40EXV1 FHYC50EXV1...
  • Page 6 Nomenclature Outdoor Unit R(Y) Classifi cation Nomenclature R10CXV1 R10CGXV1 R15CXV1 R15CGXV1 R20CXV1 R20CGXV1 R25CXV1 R25CGXV1 R28CXV1 R28CGXV1 R35DXV1 R35DGXV1 R40DXV1 R40DGXV1 R40DXY1 R40DGXY1 R50DXY1 R50DGXY1 RY10CXV1 RY10CGXV1 RY15CXV1 RY15CGXV1 RY18CXV1 RY18CGXV1 RY20CXV1 RY20CGXV1 RY25CXV1 RY25CGXV1 RY28CXV1 RY28CGXV1 RY35DXV1 RY35DGXV1 RY40DXV1 RY40DGXV1 RY40DXY1 RY40DGXY1...
  • Page 7: Application Information

    Application Information Application Information Operating Range Ensure the operating temperature is in allowance range. Cooling Outdoor DB (°C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. Indoor WB (°C) Heating Outdoor WB (°C)
  • Page 8: Refrigerant Circuit Diagrams (C Series)

    Application Information Refrigerant Circuit Diagrams (C Series) Model: FF10CXV1 – R10CXV1 / FF15CXV1 – R15CXV1 / FF20CXV1 – R20CXV1 COOLING OPERATION 3 WAY VALVE DISCHARGE COMPRESSOR COOLING CAP TUBE 2 WAY VALVE STRAINER INDOOR UNIT OUTDOOR UNIT Model: FFY10CXV1 – RY10CXV1 / FFY20CXV1 – RY18CXV1 COOLING OPERATION PIPING HEATING OPERATION...
  • Page 9 Application Information Model: FFY15CXV1 – RY15CXV1 / FFY20CXV1 – RY20CXV1 COOLING OPERATION PIPING HEATING OPERATION 3 WAY VALVE 4 WAY VALVE DISCHARGE COMPRESSOR HEATING CAP TUBE PIPING LIQUID COOLING & HEATING CAP TUBE 2 WAY STRAINER STRAINER VALVE CHECK VALVE INDOOR UNIT OUTDOOR UNIT...
  • Page 10: Refrigerant Circuit Diagrams (E Series)

    Application Information Refrigerant Circuit Diagrams (E Series) Model: FHC20EXV1 – R20CXV1 COOLING OPERATION 3 WAY VALVE DISCHARGE COMPRESSOR COOLING CAP TUBE 2 WAY VALVE STRAINER INDOOR UNIT OUTDOOR UNIT Model: FHC25EXV1 – R25CXV1 COOLING OPERATION 3 WAY VALVE COMPRESSOR COOLING CAP TUBE 3 WAY STRAINER...
  • Page 11 Application Information Model: FHC28EXV1 – R28CXV1 COOLING OPERATION 3 WAY VALVE COMPRESSOR COOLING CAP TUBE 3 WAY STRAINER VALVE INDOOR UNIT OUTDOOR UNIT Model: FHC40EXV1 – R35DXV1 / FHC40EXV1 – R40DXV1 / FHC40EXV1 – R40DXY1 / FHC50EXV1 – R50DXY1 COOLING OPERATION 3 WAY VALVE HIGH...
  • Page 12 Application Information Model: FHYC20EXV1 – RY20CXV1 COOLING OPERATION PIPING HEATING OPERATION 3 WAY VALVE 4 WAY VALVE DISCHARGE COMPRESSOR HEATING CAP TUBE PIPING LIQUID COOLING & HEATING CAP TUBE 2 WAY STRAINER STRAINER VALVE CHECK VALVE INDOOR UNIT OUTDOOR UNIT Model: FHYC25EXV1 –...
  • Page 13 Application Information Model: FHYC40EXV1 – RY35DXV1 COOLING OPERATION HEATING OPERATION PIPING 3 WAY VALVE 4 WAY VALVE HIGH PRESSURE SWITCH DISCHARGE COMPRESSOR ACCUMULATOR BIFLOW PIPING LIQUID 3 WAY STRAINER STRAINER VALVE COOLING & HEATING CAP TUBE INDOOR UNIT OUTDOOR UNIT Model: FHYC40EXV1 –...
  • Page 14: Installation Guideline

    Application Information Installation Guideline Safety Precautions • Installation and maintenance should be performed Please take note of the following important points by qualifi ed persons who are familiar with local code when installing. and regulation, and experienced with this type of •...
  • Page 15 Application Information 1) Indoor Installation Clearance Clearance must be provided for the indoor unit from wall and obstacles as shown in fi gure below. Min 0.5 m Min 0.5 m Min 0.5 m Obstacles Floor The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or more. 2) Outdoor Installation Clearance Outdoor unit must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air fl...
  • Page 16: Cooling Only

    Application Information 3) Cable Size Cooling only FF10/15CXV1 FF20CXV1 FHC20EXV1 Model Unit R10/15CXV1 R20CXV1 R20CXV1 Power supply cable size mm² Number of wire Interconnection cable size mm² Number of wire Recommended fuse FHC25EXV1 FHC28EXV1 FHC40EXV1 Model Unit R25CXV1 R28CXV1 R35DXV1 Power supply cable size Number of wire Interconnection cable size...
  • Page 17 Application Information 4) Refrigerant Piping Maximum Piping Length and Maximum Number of Bends When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant fl ow increases, thus lowering the cooling capacity, and as the result the compressor may become defective.
  • Page 18 Application Information 5) Additional Charge • The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional refrigerant charge after vacuuming is not necessary. • When the piping length is more than 7.6m, please use the table below (unit in gram). Cooling Only Indoor FF10CXV1...
  • Page 19: Sound Data

    Sound Data Sound Data Sound Pressure Level 1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FF(Y)10CXV1 High FF(Y)15CXV1 High FF(Y)20CXV1 High FH(Y)C20EXV1 Quiet High FH(Y)C25EXV1 Quiet High FH(Y)C28EXV1 Quiet High...
  • Page 20: Nc Curve

    Sound Data NC Curve FF(Y)10CXV1 FF(Y)10CXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FF(Y)15CXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 21 Sound Data FF(Y)20CXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FH(Y)C20EXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 22 Sound Data FH(Y)C25EXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FH(Y)C28EXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 23 Sound Data FH(Y)C40EXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FH(Y)C50EXV1 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 24: Engineering & Physical Data

    Engineering & Physical Data Engineering & Physical Data Engineering Data - R22 MODEL INDOOR UNIT FF10CXV1 FF15CXV1 FF20CXV1 MODEL OUTDOOR UNIT R10CXV1 R15CXV1 R20CXV1 Btu/h 9500 12500 19000 NOMINAL COOLING CAPACITY 2780 3660 5570 NOMINAL TOTAL INPUT POWER (COOLING) 1206 1832 NOMINAL RUNNING CURRENT (COOLING) 4.10...
  • Page 25 Engineering & Physical Data Engineering Data - R22 MODEL INDOOR UNIT FHC20EXV1 FHC25EXV1 FHC28EXV1 FHC40EXV1 MODEL OUTDOOR UNIT R20CXV1 R25CXV1 R28CXV1 R35CXV1 Btu/h 19500 25000 27000 35000 NOMINAL COOLING CAPACITY 5715 7327 7913 10258 NOMINAL TOTAL INPUT POWER (COOLING) 1960 2540 2720 3010...
  • Page 26 Engineering & Physical Data Engineering Data - R22 MODEL INDOOR UNIT FHC40EXV1 FHC50EXV1 MODEL OUTDOOR UNIT R40DXV1 R40DXY1 R50DXY1 Btu/h 39000 39500 49500 NOMINAL COOLING CAPACITY 11430 11600 14500 NOMINAL TOTAL INPUT POWER (COOLING) 3450 3650 4600 NOMINAL RUNNING CURRENT (COOLING) 16.7 6.13 8.00...
  • Page 27: Safety Device

    Engineering & Physical Data Safety Device INDOOR FF(Y)10/15EXV1 FF(Y)20CXV1 MODEL OUTDOOR R(Y)10/15CXV1 RY18CXV1 R(Y)20CXV1 TYPE HIGH PRESSURE OPEN kPa / psi SWITCH CLOSE kPa / psi TYPE SAFETY LOW PRESSURE DEVICE OPEN kPa / psi SWITCH CLOSE kPa / psi PHASE SEQUENCER DISC.
  • Page 28 Engineering & Physical Data INDOOR FHYC40EXV1 MODEL OUTDOOR RY35DXV1 RY40DXV1 RY40DXY1 TYPE HIGH PRESSURE OPEN kPa / psi 2937 / 426 SWITCH CLOSE kPa / psi 2413 / 350 TYPE SAFETY LOW PRESSURE DEVICE OPEN kPa / psi SWITCH CLOSE kPa / psi PHASE SEQUENCER DISC.
  • Page 29: Performance Data

    Performance Data Performance Data Calculation Steps Interpolation method can be used to get the total Solution: cooling capacity, TC and sensible cooling capacity, Based on the Performance Table, SC and power input, PI at those temperatures which 1. Refer to the Indoor DB column, are not stated out in the table.
  • Page 30 Performance Data (b) Indoor Condition: 25°C DB, 16°C WB By Interpolation Method Outdoor Condition: 35°C DB 25°C – 24°C – 3.51kW ⇒ Outdoor temperature 27°C – 24°C 3.52kW – 3.51kW 35°C ⇒ x = 3.51kW Similarly, = 2.71kW 3.51 2.57 1.29 = 1.29kW 3.52...
  • Page 31: Performance Tables

    Performance Data Performance Tables Cooling Only Model: FF10CXV1 - R10CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 2.62 1.90 0.70 2.53 1.85 0.76 2.43 1.80 0.82 2.34 1.75 0.89 2.15 1.63 0.96 1.98 1.53 1.06 24°C 2.63 2.28 0.70 2.53 2.23 0.76 2.44 2.18 0.82 2.34 2.12 0.89 2.15 1.98 0.96 1.99 1.87 1.06 16°C...
  • Page 32 Performance Data Model: FF15CXV1 - R15CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 3.45 2.51 0.92 3.33 2.44 0.99 3.21 2.38 1.07 3.08 2.31 1.16 2.83 2.15 1.26 2.61 2.02 1.39 24°C 3.46 3.00 0.92 3.33 2.94 0.99 3.21 2.87 1.07 3.08 2.80 1.16 2.83 2.61 1.26 2.62 2.46 1.39 16°C 27°C 3.48 3.41 0.92 3.37 3.33 0.99 3.25 3.25 1.08 3.13 3.13 1.17 2.88 2.88 1.27 2.68 2.68 1.40...
  • Page 33 Performance Data Model: FF20CXV1 - R20CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 5.25 3.47 1.39 5.07 3.38 1.50 4.88 3.29 1.63 4.68 3.19 1.77 4.30 2.97 1.92 3.97 2.80 2.11 24°C 5.26 4.15 1.39 5.07 4.06 1.50 4.88 3.96 1.63 4.69 3.87 1.77 4.31 3.61 1.92 3.98 3.41 2.11 16°C 27°C 5.30 4.71 1.39 5.12 4.60 1.51 4.94 4.49 1.63 4.76 4.38 1.77 4.39 4.08 1.92 4.08 3.83 2.12...
  • Page 34 Performance Data Model: FHC20EXV1 - R20CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 5.39 4.01 1.49 5.20 3.91 1.61 5.01 3.80 1.74 4.81 3.69 1.89 4.41 3.44 2.05 4.08 3.23 2.26 24°C 5.40 4.80 1.49 5.21 4.69 1.61 5.02 4.58 1.74 4.81 4.47 1.89 4.42 4.17 2.05 4.09 3.94 2.26 16°C 27°C 5.44 5.44 1.49 5.26 5.26 1.61 5.08 5.08 1.75 4.89 4.89 1.90 4.51 4.51 2.06 4.19 4.19 2.27...
  • Page 35 Performance Data Model: FHC25EXV1 - R25CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 6.91 4.63 1.93 6.67 4.51 2.09 6.42 4.38 2.26 6.16 4.26 2.45 5.66 3.96 2.66 5.22 3.73 2.93 24°C 6.92 5.54 1.93 6.68 5.41 2.09 6.43 5.29 2.26 6.17 5.16 2.45 5.67 4.81 2.66 5.24 4.54 2.93 16°C 27°C 6.98 6.28 1.93 6.74 6.14 2.09 6.51 5.99 2.27 6.26 5.84 2.46 5.78 5.43 2.67 5.38 5.10 2.94...
  • Page 36 Performance Data Model: FHC28EXV1 - R28CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 7.46 5.42 2.07 7.19 5.27 2.24 6.93 5.13 2.42 6.65 4.99 2.62 6.10 4.64 2.85 5.64 4.36 3.14 24°C 7.47 6.49 2.07 7.20 6.34 2.24 6.94 6.19 2.42 6.66 6.04 2.63 6.12 5.64 2.85 5.66 5.32 3.14 16°C 27°C 7.53 7.35 2.07 7.28 7.19 2.24 7.02 7.02 2.43 6.76 6.76 2.63 6.23 6.23 2.86 5.80 5.80 3.15...
  • Page 37 Performance Data Model: FHC40EXV1 - R35DXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 9.67 6.94 2.29 9.33 6.76 2.47 8.98 6.57 2.68 8.62 6.38 2.90 7.92 5.94 3.15 7.31 5.59 3.47 24°C 9.69 8.31 2.29 9.34 8.12 2.47 9.00 7.93 2.68 8.64 7.73 2.91 7.93 7.22 3.15 7.34 6.81 3.48 16°C 27°C 9.76 9.42 2.29 9.44 9.20 2.48 9.11 8.99 2.68 8.76 8.76 2.91 8.09 8.09 3.16 7.52 7.52 3.49...
  • Page 38 Performance Data Model: FHC40EXV1 - R40DXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 10.78 7.53 2.62 10.39 7.34 2.83 10.01 7.14 3.07 9.61 6.93 3.33 8.82 6.45 3.61 8.14 6.07 3.98 24°C 10.79 9.02 2.62 10.41 8.81 2.84 10.02 8.61 3.07 9.62 8.39 3.33 8.84 7.84 3.61 8.18 7.40 3.98 16°C 27°C 10.88 10.23 2.63 10.51 9.99 2.84 10.14 9.76 3.08 9.76 9.51 3.34 9.01 8.85 3.62 8.38 8.31 4.00 30°C 11.21 11.21 2.64 10.89 10.89 2.86 10.56 10.56 3.10 10.22 10.22 3.36 9.47 9.47 3.65 8.86 8.86 4.04...
  • Page 39 Performance Data Model: FHC40EXV1 - R40DXY1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 10.94 7.43 2.77 10.55 7.23 3.00 10.16 7.04 3.25 9.75 6.84 3.52 8.95 6.36 3.82 8.27 5.98 4.21 24°C 10.95 8.89 2.77 10.56 8.69 3.00 10.17 8.49 3.25 9.76 8.28 3.52 8.97 7.73 3.82 8.30 7.29 4.21 16°C 27°C 11.04 10.08 2.78 10.67 9.85 3.01 10.29 9.62 3.26 9.91 9.37 3.53 9.14 8.72 3.83 8.51 8.19 4.23 30°C 11.38 11.38 2.79 11.05 11.05 3.02 10.72 10.72 3.28 10.37 10.37 3.56 9.61 9.61 3.87 8.99 8.99 4.27...
  • Page 40 Performance Data Model: FHC50EXV1 - R50DXY1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 13.67 9.29 3.50 13.19 9.04 3.78 12.70 8.80 4.09 12.19 8.55 4.44 11.19 7.96 4.82 10.33 7.48 5.31 24°C 13.69 11.12 3.50 13.20 10.87 3.78 12.72 10.61 4.10 12.21 10.35 4.44 11.22 9.67 4.82 10.37 9.12 5.31 16°C 27°C 13.80 12.61 3.50 13.34 12.32 3.79 12.87 12.03 4.10 12.39 11.72 4.45 11.43 10.91 4.83 10.63 10.25 5.33 30°C 14.22 14.22 3.52 13.82 13.82 3.81 13.40 13.40 4.13 12.97 12.97 4.49 12.02 12.02 4.87 11.24 11.24 5.38...
  • Page 41 Performance Data Heatpump Model: FFY10CXV1 - RY10CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 2.62 1.90 0.70 2.53 1.85 0.76 2.43 1.80 0.82 2.34 1.75 0.89 2.15 1.63 0.96 1.98 1.53 1.06 24°C 2.63 2.28 0.70 2.53 2.23 0.76 2.44 2.18 0.82 2.34 2.12 0.89 2.15 1.98 0.96 1.99 1.87 1.06 16°C 27°C 2.65 2.59 0.70 2.56 2.53 0.76 2.47 2.47 0.82 2.37 2.37 0.89 2.19 2.19 0.97 2.04 2.04 1.07...
  • Page 42 Performance Data Model: FFY15CXV1 - RY15CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 3.45 2.51 0.92 3.33 2.44 0.99 3.21 2.38 1.07 3.08 2.31 1.16 2.83 2.15 1.26 2.61 2.02 1.39 24°C 3.46 3.00 0.92 3.33 2.94 0.99 3.21 2.87 1.07 3.08 2.80 1.16 2.83 2.61 1.26 2.62 2.46 1.39 16°C 27°C 3.48 3.41 0.92 3.37 3.33 0.99 3.25 3.25 1.08 3.13 3.13 1.17 2.88 2.88 1.27 2.68 2.68 1.40...
  • Page 43 Performance Data Model: FFY20CXV1 - RY18CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 4.98 3.29 1.40 4.80 3.21 1.51 4.62 3.12 1.64 4.44 3.03 1.78 4.08 2.82 1.93 3.76 2.65 2.12 24°C 4.99 3.94 1.40 4.81 3.85 1.51 4.63 3.76 1.64 4.44 3.67 1.78 4.08 3.43 1.93 3.78 3.23 2.12 16°C 27°C 5.02 4.47 1.40 4.86 4.37 1.51 4.69 4.26 1.64 4.51 4.15 1.78 4.16 3.87 1.93 3.87 3.63 2.13...
  • Page 44 Performance Data Model: FFY20CXV1 - RY20CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 5.25 3.47 1.39 5.07 3.38 1.50 4.88 3.29 1.63 4.68 3.19 1.77 4.30 2.97 1.92 3.97 2.80 2.11 24°C 5.26 4.15 1.39 5.07 4.06 1.50 4.88 3.96 1.63 4.69 3.87 1.77 4.31 3.61 1.92 3.98 3.41 2.11 16°C 27°C 5.30 4.71 1.39 5.12 4.60 1.51 4.94 4.49 1.63 4.76 4.38 1.77 4.39 4.08 1.92 4.08 3.83 2.12...
  • Page 45 Performance Data Model: FHYC20EXV1 - RY20CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 5.39 4.01 1.49 5.20 3.91 1.61 5.01 3.80 1.74 4.81 3.69 1.89 4.41 3.44 2.05 4.08 3.23 2.26 24°C 5.40 4.80 1.49 5.21 4.69 1.61 5.02 4.58 1.74 4.81 4.47 1.89 4.42 4.17 2.05 4.09 3.94 2.26 16°C 27°C 5.44 5.44 1.49 5.26 5.26 1.61 5.08 5.08 1.75 4.89 4.89 1.90 4.51 4.51 2.06 4.19 4.19 2.27...
  • Page 46 Performance Data Model: FHYC25EXV1 - RY25CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 6.91 4.63 1.93 6.67 4.51 2.09 6.42 4.38 2.26 6.16 4.26 2.45 5.66 3.96 2.66 5.22 3.73 2.93 24°C 6.92 5.54 1.93 6.68 5.41 2.09 6.43 5.29 2.26 6.17 5.16 2.45 5.67 4.81 2.66 5.24 4.54 2.93 16°C 27°C 6.98 6.28 1.93 6.74 6.14 2.09 6.51 5.99 2.27 6.26 5.84 2.46 5.78 5.43 2.67 5.38 5.10 2.94...
  • Page 47 Performance Data Model: FHYC28EXV1 - RY28CXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 7.46 5.42 2.07 7.19 5.27 2.24 6.93 5.13 2.42 6.65 4.99 2.62 6.10 4.64 2.85 5.64 4.36 3.14 24°C 7.47 6.49 2.07 7.20 6.34 2.24 6.94 6.19 2.42 6.66 6.04 2.63 6.12 5.64 2.85 5.66 5.32 3.14 16°C 27°C 7.53 7.35 2.07 7.28 7.19 2.24 7.02 7.02 2.43 6.76 6.76 2.63 6.23 6.23 2.86 5.80 5.80 3.15...
  • Page 48 Performance Data Model: FHYC40EXV1 - RY35DXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 9.67 6.94 2.29 9.33 6.76 2.47 8.98 6.57 2.68 8.62 6.38 2.90 7.92 5.94 3.15 7.31 5.59 3.47 24°C 9.69 8.31 2.29 9.34 8.12 2.47 9.00 7.93 2.68 8.64 7.73 2.91 7.93 7.22 3.15 7.34 6.81 3.48 16°C 27°C 9.76 9.42 2.29 9.44 9.20 2.48 9.11 8.99 2.68 8.76 8.76 2.91 8.09 8.09 3.16 7.52 7.52 3.49...
  • Page 49: Heating Mode

    Performance Data Model: FHYC40EXV1 - RY40DXV1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 10.94 7.53 2.74 10.55 7.34 2.96 10.16 7.14 3.20 9.75 6.93 3.47 8.95 6.45 3.77 8.27 6.07 4.15 24°C 10.95 9.02 2.74 10.56 8.81 2.96 10.17 8.61 3.20 9.76 8.39 3.48 8.97 7.84 3.77 8.30 7.40 4.16 16°C 27°C 11.04 10.23 2.74 10.67 9.99 2.96 10.29 9.76 3.21 9.91 9.51 3.48 9.14 8.85 3.78 8.51 8.31 4.17 30°C 11.38 11.38 2.75 11.05 11.05 2.98 10.72 10.72 3.23 10.37 10.37 3.51 9.61 9.61 3.81 8.99 8.99 4.21...
  • Page 50 Performance Data Model: FHYC40EXV1 - RY40DXY1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 10.94 7.43 2.66 10.55 7.23 2.88 10.16 7.04 3.11 9.75 6.84 3.38 8.95 6.36 3.66 8.27 5.98 4.04 24°C 10.95 8.89 2.66 10.56 8.69 2.88 10.17 8.49 3.12 9.76 8.28 3.38 8.97 7.73 3.67 8.30 7.29 4.04 16°C 27°C 11.04 10.08 2.66 10.67 9.85 2.88 10.29 9.62 3.12 9.91 9.37 3.39 9.14 8.72 3.68 8.51 8.19 4.06 30°C 11.38 11.38 2.68 11.05 11.05 2.90 10.72 10.72 3.14 10.37 10.37 3.41 9.61 9.61 3.71 8.99 8.99 4.09...
  • Page 51 Performance Data Model: FHYC50EXV1 - RY50DXY1 Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 13.30 9.03 3.65 12.83 8.79 3.94 12.35 8.56 4.27 11.85 8.31 4.63 10.88 7.73 5.02 10.05 7.28 5.54 24°C 13.31 10.81 3.65 12.84 10.56 3.95 12.36 10.32 4.27 11.87 10.06 4.63 10.91 9.40 5.03 10.09 8.87 5.54 16°C 27°C 13.42 12.26 3.65 12.97 11.98 3.95 12.52 11.70 4.28 12.04 11.40 4.64 11.11 10.61 5.04 10.34 9.96 5.56 30°C 13.83 13.83 3.67 13.43 13.43 3.97 13.03 13.03 4.31 12.61 12.61 4.68 11.69 11.69 5.08 10.93 10.93 5.62...
  • Page 52: Outline & Dimension

    Outline & Dimension Outline & Dimension Indoor Unit Model: FF(Y)10/15/20CXV1 Note: Dimension in mm Model: FH(Y)C20/25/28/40/50EXV1 Dimension Model FH(Y)C20/25/28EXV1 FH(Y)C40/50EXV1 Note: Dimension in mm...
  • Page 53: Outdoor Unit

    Outline & Dimension Outdoor Unit Model: R(Y)10/15CXV1 Dimension Model R(Y)10/15CXV1 700 521 250 478 175 36 95 94 86 68 440 130 110 15 21 19 278 80 65 Note: Dimension in mm Model: RY18CXV1 / R(Y)20/25/28CXV1 Dimension Model RY18CXV1 / R(Y)20CXV1 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75 R(Y)25/28CXV1 855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75 Note: Dimension in mm...
  • Page 54: Model

    Outline & Dimension Model: R(Y)35/40DXV1 / R(Y)40/50DXY1 MADE IN MALAYSIA Dimension Model R(Y)35/40DXV1 / 1030 826 400 410 746 142 R(Y)40/50DXY1 Note: Dimension in mm...
  • Page 55: Wiring Diagram

    Wiring Diagram Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model: FF10/15CXV1 Model: R10/15CXV1...
  • Page 56: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FF20CXV1 Model: R20CXV1...
  • Page 57: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHC20/25/28EXV1 Model: R20/25/28CXV1 FLOAT SWITCH INDOOR COIL SENSOR WIRED ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING. PINK PINK AS - AIR SWING MOTOR. BROWN BROWN DP - DRAIN PUMP.
  • Page 58: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHC40EXV1 Model: R35/40DXV1 FLOAT SWITCH INDOOR COIL SENSOR WIRED ID ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING AS - AIR SWING MOTOR PINK PINK DP - DRAIN PUMP BROWN...
  • Page 59: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHC40/50EXV1 Model: R40/50DXY1 FLOAT SWITCH INDOOR COIL SENSOR WIRED ID ROOM CONTROLLER DISPLAY BOARD T FULL CN_WIR INDOOR AIR SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING AS - AIR SWING MOTOR PINK PINK DP - DRAIN PUMP BROWN...
  • Page 60: Model

    Wiring Diagram Heatpump Indoor Unit Outdoor Unit Model: FFY10/15CXV1 Model: RY10/15CXV1 WIRED OR WIRELESS RETURN AIR SENSOR REMOTE CONTROLLER ROOM INDOOR COIL SENSOR TRANSFORMER OUTDOOR COIL SENSOR TWIN T-FULL FLOAT SWITCH HIGH MED PURPLE PURPLE ORANGE ORANGE BROWN BROWN BLUE BLUE BLUE BLUE...
  • Page 61: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FFY20CXV1 Model: RY18/20CXV1 WIRED OR WIRELESS RETURN AIR SENSOR REMOTE CONTROLLER ROOM INDOOR COIL SENSOR TRANSFORMER OUTDOOR COIL SENSOR TWIN T-FULL FLOAT SWITCH HIGH MED PURPLE PURPLE ORANGE ORANGE BROWN BROWN BLUE BLUE BLUE BLUE BLUE...
  • Page 62: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHYC20/25/28EXV1 Model: RY20/25/28CXV1 FLOAT SWITCH INDOOR COIL SENSOR WIRED ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR TO OUTDOOR DEFROST SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING PINK PINK AS - AIR SWING MOTOR BROWN BROWN DP - DRAIN PUMP...
  • Page 63: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHYC40EXV1 Model: RY35/40DXV1 FLOAT SWITCH INDOOR COIL SENSOR WIRED ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR TO OUTDOOR DEFROST SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING AS - AIR SWING MOTOR DP - DRAIN PUMP PINK PINK...
  • Page 64: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHYC40EXV1 Model: RY40DXY1 FLOAT SWITCH WIRED INDOOR COIL SENSOR ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR TO OUTDOOR DEFROST SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING AS - AIR SWING MOTOR DP - DRAIN PUMP PINK PINK...
  • Page 65: Model

    Wiring Diagram Indoor Unit Outdoor Unit Model: FHYC50EXV1 Model: RY50DXY1 FLOAT SWITCH WIRED INDOOR COIL SENSOR ROOM DISPLAY BOARD CONTROLLER T FULL CN_WIR INDOOR AIR SENSOR TO OUTDOOR DEFROST SENSOR CN STP COMP. KEY: FIELD SUPPLY WIRING AS - AIR SWING MOTOR DP - DRAIN PUMP PINK PINK...
  • Page 66: Service & Maintenance

    Service & Maintenance Service & Maintenance • Disconnect from main supply before servicing the air conditioner. • The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Maintenance Procedures Period...
  • Page 67: Model

    Service & Maintenance Pre Start Up Maintenance (After Extended Shutdown) Inspect thoroughly and clean indoor and outdoor units. Clean or replace air fi lters. Clean condensates drain line. Clean clogged indoor and outdoor coils. Check fan imbalance before operation. Tighten all wiring connections and panels. Check for refrigerant leakage.
  • Page 68: Troubleshooting

    Troubleshooting Troubleshooting Indicator Lights LED Indicator Light Display - Cooling Only LED Indicator Light Display - Heatpump POWER TIMER SLEEP POWER TIMER HEAT / SLEEP LED Light Diagnostic Table Error Operation / Action Code Faulty Indication GREEN ORANGE Cooling mode Timer On Sleep mode On Heating mode...
  • Page 69: High

    Troubleshooting Phase Sequencer The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase sequencer) is fi tted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase sequencer operates, and the unit will not start. This device is located in the control box of the outdoor unit.
  • Page 70: High

    Troubleshooting Error Code / Fault Condition When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
  • Page 71: High

    Troubleshooting Diagnostic Guidelines By means of pressure readings: Data Pressure Probable cause Circuit High side • 1. Overcharged with refrigerant. Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air). 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit. •...

This manual is also suitable for:

Fhc-eFhyc-eFfy-c

Table of Contents