Technical Data; Sunny Island 8.0H - SMA SUNNY ISLAND 8.0H Installation Manual

Off-grid inverter
Hide thumbs Also See for SUNNY ISLAND 8.0H:
Table of Contents

Advertisement

12  Technical Data

12 Technical Data

12.1 Sunny Island 8.0H
AC1 Connection, Stand-Alone Grid
Rated power
Maximum AC power
AC power for 30 minutes at 25°C
AC power for 5 minutes at 25°C
AC power for 1 minute at 25°C
Maximum AC power for 3 seconds at 25°C
Maximum connectable power of the PV inverters*
Maximum connectable power of the wind power inverters*
Rated grid voltage
AC voltage range
Rated frequency
Frequency range
Frequency tolerance of the set range
Rated current
Maximum output current as a peak value for 60 milliseconds
Total harmonic factor of the output voltage
Displacement power factor cos φ
Recommended conductor cross-section
Maximum connectable conductor cross-section
Cable diameter
AC1 terminal
Trippable miniature circuit-breakers for selectivity
* For every 1,000 W of power of the wind power inverters, the maximum connectable power of the PV inverters decreases
by 2,000 W.
144
SI80H-60H-OffGrid-IA-en-11
SMA Solar Technology AG
6,000 W
12,000 W
8,000 W
9,100 W
9,600 W
11,000 W
12,000 W
6,000 W
230 V
202 V ... 253 V
50 Hz
45 Hz ... 65 Hz
±5 Hz
26.1 A
120 A
4%
− 1 ... +1
10 mm²
16 mm²
9 mm ... 18 mm
Lever terminal
Tripping characteristics B16
Installation Manual