Generator Management Of The Off-Grid Inverter; Generator Management Tasks; Conditions For Generator Requests - SMA SUNNY ISLAND 8.0H Installation Manual

Off-grid inverter
Hide thumbs Also See for SUNNY ISLAND 8.0H:
Table of Contents

Advertisement

SMA Solar Technology AG
10.7 Generator Management of the Off-Grid Inverter
10.7.1 Generator Management Tasks
The generator management performs the following tasks:
• Requesting the generator in automatic generator mode (see Section 10.7.2 "Conditions for
Generator Requests", page 131):
– Requesting the generator depending on the state of charge
– Requesting the generator depending on the load
– Requesting the generator in a time-controlled manner
– Requesting the generator depending on the charging process
• Controlling the off-grid inverter for switching the stand-alone grid to the generator voltage
(see Section 10.4 "Synchronisation of the Stand-Alone Grid to the External Energy
Source", page 130)
• Observing generator run times in order to prolong the generator's service life
(see Section 10.7.3 "Generator Run Times", page 132)
• Protecting the generator against overload and backfeed (see Section 10.7.4 "Electrical Limiting
Values for the Generator", page 133)
• Controlling the off-grid inverters when disconnecting the generator
• Supplying reactive power for the generator
10.7.2 Conditions for Generator Requests
To adjust generator management to the requirements of the off-grid system, you can change the

conditions for generator requests.

Generator request
State-of-charge-dependent
generator request
Load-dependent generator
request
Installation Manual
Explanation
Depending on the state of charge of the battery, the generator
management requests the generator so that it will recharge the
battery. In this way, the generator management prevents the
battery from discharging too much. Tip: You can also configure
the generator request depending on the time of day, e.g. to avoid
starting the generator at night where possible.
If the consumption load in the stand-alone grid exceeds a
configured limit, generator management requests the generator.
The generator then supplies the loads. This reduces the load on
the battery.
If necessary, the loads in the stand-alone grid are supplied by the
generator and the off-grid inverter together. The sum of both
powers is available to the stand-alone grid.
10  External Energy Sources in the Off-Grid System
SI80H-60H-OffGrid-IA-en-11
131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny island 6.0h

Table of Contents