13. Setting the maximum permissible current for an off-grid system with the electricity grid:
• Select the 003.21 GdCurNom parameter and
press the button.
• Set the maximum permissible current and press the button.
• Confirm the maximum current with Y.
14. Setting the maximum generator current for an off-grid system with a generator:
• Select the 003.22 GnCurNom parameter and
press the button.
• Set the maximum current for permanent loading of the generator and press the button.
• Confirm the maximum current with Y.
15. Setting the type of the generator interface for an off-grid system with a generator:
• Select the 003.23 GnStrMod parameter and
press the button.
• If the generator does not have an electric starting device, set Manual and press the button.
• If the generator can be started and stopped using one contact, set Autostart and press the
button.
• If the generator is controlled using GenMan, set GenMan and press the button.
• Confirm the generator interface with Y.
16. Setting the earthing system of the off-grid system:
• Select the 003.24 GndTyp parameter and
press the button.
• For a TN system, set TN and confirm the entry.
• For a TT system, set TT and confirm.
• Confirm the earthing system with Y.