12 Technical Data
High-level digital input
Low-level digital input
Galvanically insulated control contacts
AC load-switching limit for multi-function relays 1 and 2
DC load-switching limit for multi-function relays 1 and 2
DC Load-Limitation Curve
Figure 31: DC load-limitation curve for multi-function relays 1 and 2
General Data
Width x height x depth
Weight
Operating temperature range
Storage temperature range
Humidity
Maximum installation height above MSL
Topology
Cooling concept
Protection class according to IEC 62103
Climatic category according to IEC 60721
Degree of protection according to IEC 60529
148
SI80H-60H-OffGrid-IA-en-11
SMA Solar Technology AG
9 V ... 63 V
0 V ... 3 V
2 multi-function relays
1 A at 250 V
See DC load-limitation curve
467 mm x 612 mm x 242 mm
63 kg
− 25°C ... +60°C
− 25°C ... +70°C
0% ... 100%
3,000 m
LF transformer
OptiCool
I
3K6
IP54
Installation Manual