7  Commissioning
6. Setting the battery type:
• Select the 003.06 BatTyp parameter and
press the button.
• If the battery type is FLA, set FLA and press the button.
• If the battery type is VRLA, set VRLA and press the button.
• Confirm the battery type with Y.
7. Setting the battery voltage:
• Select the 003.07 BatVtgLst parameter and
press the button.
• Set the battery voltage and press the button.
• Confirm the battery voltage with Y.
8. Setting the battery capacity:
• Select the 003.09 BatCpyNom parameter
and press the button.
• Set the C10 battery capacity and press the button (see Section 7.4.1 "Determining the
Battery Capacity", page 75).
• Confirm the battery capacity with Y.
9. Setting the line voltage and power frequency:
• Select the 003.14 AcVtgFrqTyp parameter
and press the button.
• For a line voltage of 230 V and 50 Hz, set 230V_50Hz and press the button.
• For a line voltage of 220 V and 60 Hz, set 220V_60Hz and press the button.
• Confirm the line voltage and power frequency with Y.