Eaton Powerware 5125 Installation Manual page 32

Installation guide for ibm applications
Hide thumbs Also See for Powerware 5125:
Table of Contents

Advertisement

COMMUNICATION
Table 9. Communication Port Pin Assignment
Pin Number
Signal Name
1
Low Batt
2
TxD
3
RxD
4
DTR
5
GND
6
DSR
7
RTS
8
AC Fail
9
Power Source
The On-Bypass Relay Contact. You can enable the On-Bypass relay using
the jumper on the Single-Port Card. The jumper default is disabled. To
enable the On-Bypass relay:
1.
2.
28
EATON Powerware
Function
Low Battery relay contact
Transmit to external device
Receive from external device
PnP (Plug and Play) from external device (tied to Pin 6)
Signal common (tied to chassis)
To external device (tied to Pin 4)
PnP from external device (default) or On Bypass relay
contact (jumper-selectable)
AC Fail relay contact
+V (8 to 24 volts DC power)
Remove the Single-Port Card on the UPS rear panel. Retain the
screws (see Figure 25).
Figure 25. Removing the Single-Port Card
Move the J3 jumper to the AS/400
On-Bypass relay as shown in Figure 26.
®
5125 (9910-E33) UPS Installation Guide for IBM
Direction from the UPS
Out
Out
In
In
Out
In / Out
Out
Out
position to enable the
®
®
S
Applications
164201695 Rev 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 5125 9910-e33

Table of Contents