NOTE The redundant power source must be protected with Transient Voltage Surge
Suppression (TVSS).
2.
Insert the supplied cord retention clips by each output receptacle
that will be used (see Figure 17).
3.
Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 20 for more information on load segments).
Table 6. Plug Types Supported
IBM Plug Type
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high
power requirements of the heating elements.
NOTE To prevent an overload alarm, verify that the total equipment ratings do not exceed
the UPS capacity.
4.
Bend and twist the cord retention clips around the equipment
power cords to secure the cord connections (see Figure 17).
5.
If you installed an optional EBM(s), remove the breaker tie from all
battery circuit breakers.
Switch all battery circuit breakers to the ON (
®
EATON Powerware
5125 (9910-E33) UPS Installation Guide for IBM
Figure 17. Attaching the Cord Retention Clips
Description
IEC 320-C14
IEC 320-C20
®
Applications
INSTALLATION
Quantity Supported
9
1
|
) position.
S
15
164201695 Rev 1