Dc Voltage / Current Sensor Abnormality - Daikin FTXS20K2V1B Service Manual

Inverter pair wall mounted type ftxs/atxs-k series
Hide thumbs Also See for FTXS20K2V1B:
Table of Contents

Advertisement

SiBE041134EB

4.20 DC Voltage / Current Sensor Abnormality

H8
Error Code
Method of Error
DC voltage or DC current sensor abnormality is identified based on the compressor running
frequency and the input current.
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the outdoor unit PCB (main PCB).
Service Diagnosis
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Troubleshooting