Environmental Specifications
007-5832-002
Table A-3 lists the environmental specifications of the system.
Table A-3
Environmental Specifications
Feature
Temperature tolerance
(operating)
Temperature tolerance
(non-operating)
Relative humidity
Heat dissipation full
SGI UV 2000 (rack)
Cooling requirement
Air flow: intake (front),
exhaust (rear)
Maximum altitude
Specification
+5 C (41 F) to +35 C (95 F) (up to 1500 m / 5000 ft.)
+5 C (41 F) to +30 C (86 F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)
-40 C (-40 F) to +60 C (140 F)
10% to 80% operating (no condensation)
8% to 95% non-operating (no condensation)
115.6 kBTU/hr maximum (based on 33.88 kW) approximate
Ambient air or optional water cooling
Approximately 2,800 CFM (normal operation)
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating
Environmental Specifications