5 Operation

There are 2 types of WD curves: slope-offset curve (default),
and 2-points curve. If needed, you can change the type in
[2.E] Main zone > WD curve type. The way to adjust the
curve depends on the type.
Slope-offset curve
Slope. When slope is changed,
the new preferred temperature at
X1 is unequally higher than the
preferred temperature at X2.
a
b
c
d
Y4
Y3
Y2
Y1
X1
X2
X1, X2
Outdoor ambient temperature
Y1~Y4
Desired leaving water temperature
a
WD curve before changes
b
WD curve after changes
c
Slope
d
Offset
Possible actions on this screen
Select slope or offset.
Increase or decrease the slope/offset.
When slope is selected: set slope and go to offset.
When offset is selected: set offset.
Confirm changes and return to the submenu.
2-points curve
Y2
Y1
X1
X2
X1, X2
Outdoor ambient temperature
Y1, Y2
Desired leaving water temperature
Possible actions on this screen
Go through the temperatures.
Change the temperature.
Go to the next temperature.
Confirm changes and proceed.
More information
For more information, see also:
"5.4 Turning operation ON or
control" [ 4  11]
"5.6 Space heating/cooling
Example" [ 4  12]
"5.7 Schedule screen:
curve" [ 4  14]
"5.8 Weather-dependent
▪ User reference guide
5
Operation
INFORMATION
Heating is only applicable in case of reversible models.
5.1

User interface: Overview

The user interface has the following components:
Operation manual
6
Offset. When offset is changed,
the new preferred temperature at
X1 is equally higher as the
preferred temperature at X2.
a
b
c
d
Y4
Y3
Y2
Y1
X1
X2
OFF" [ 4  11]
a
b
a
Slot for WLAN cartridge
b
USB connector
c
LCD screen
d
Dials and buttons
Slot for WLAN cartridge
With the WLAN cartridge, the installer can connect the system to the
internet. As user you can then control the system via the ONECTA
app. Note: This slot cannot be used for SD cards.
USB connector
With a USB memory stick, the installer can:
▪ Update the software. This requires a correct config file on the USB
memory stick.
▪ Import the settings generated by E-Configurator (Heating
Solutions Navigator) from the USB memory stick to the user
interface (MMI). This requires a correct config file on the USB
memory stick.
▪ Export the current settings (i.e. field settings, MMI EEPROM
settings, schedule timers) from the user interface (MMI) to the
USB memory stick.
LCD screen
The LCD screen has a sleeping function. After 15  min of non-
interaction with the user interface, the screen darkens. Pressing any
button or rotating any dial awakens the display.
Dials and buttons
You use the dials and buttons:
▪ To navigate through the screens, menus and settings of the LCD
screen
▪ To set values
a
b
c
d
Item
a Left dial
The LCD shows an arc on the left side of the
display when you can use the left dial.
: Turn, then press the left dial. Navigate
through the menu structure.
: Turn the left dial. Choose a menu item.
: Press the left dial. Confirm your choice
or go to a submenu.
b Back button
: Press to go back 1 step in the menu structure.
c Home
: Press to go back to the home screen.
button
c
d
e
Description
EWAA004~008D2 + EWYA004~008D2
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688015-1 – 2022.04