Mitsubishi Electric FR-A520-0.4K -55K Instruction Manual page 130

Transistorized inverter, high function & low acoustic noise
Table of Contents

Advertisement

Note: 1. The inverter station numbers may be set between H00 and H1F (stations 0 and 31) in
hexadecimal.
2. *3 indicates the control code.
3. *4 indicates the CR or LF code.
When data is transmitted from the computer to the inverter, codes CR (carriage return)
and LF (line feed) are automatically set at the end of a data group on some computers. In
this case, setting must also be made from the inverter according to the computer.
Also, the presence and absence of the CR and LF codes can be selected using Pr. 124.
4. *5: When Pr. 123 "waiting time setting" ≠ 9999, create the communication request data
with no "waiting time" in the data format. (The number of characters decreases by 1.)
2) Send data from computer to inverter during data write
[No data error detected]
Inverter
*3
Format C
station
ACK
number
1
2
3) Reply data from inverter to computer during data read
[No data error detected]
Inverter
*3
Format E
station
STX
number
1
2
3
Inverter
*3
Format E'
station
STX
number
1
2
3
4) Reply data from computer to inverter during data read
[No data error detected]
*3
Format G
ACK
1
( 4 ) Data definitions
1) Control codes
Signal
ASCII Code
STX
H02
Start of Text (Start of data)
ETX
H03
End of Text (End of data)
ENQ
H05
Enquiry (Communication request)
ACK
H06
Acknowledge (No data error detected)
LF
H0A
Line Feed
CR
H0D
Carriage Return
NAK
H15
Negative Acknowledge (Data error detected)
2) Inverter station number
Specify the station number of the inverter which communicates with the computer.
3) Instruction code
Specify the processing request (e.g. operation, monitoring) given by the computer to the inverter. Hence,
the inverter can be run and monitored in various ways by specifying the instruction code as appropriate.
4) Data
Indicates the data such as frequency and parameters transferred to and from the inverter. The definitions
and ranges of set data are determined in accordance with the instruction codes. (Refer to Appendix 1.)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
[Data error detected]
*4
Format D
←Number of characters
3
4
*3
Sum
Read data
*4
ETX
check
4
5
6
7
8
9
10
11
Read
*3
Sum
*4
data
ETX
check
←Number of characters
4
5
6
7
8
9
[Data error detected]
Inverter
Format H
station
*4
number
←Number of characters
2
3
4
Description
117
PARAMETERS
Inverter
*3
Error
station
*4
NAK
code
number
←Number of characters
1
2
3
4
5
[Data error detected]
Format F
Inverter
*3
Error
station
NAK
code
number
1
2
3
4
Inverter
*3
station
*4
NAK
number
←Number of characters
1
2
3
4
*4
5

Hide quick links: