Wiring The Fan Motor: 9 Lead, Dual Voltage, Wye Motor Configurations - BIG ASS FANS Pivot 180 Installation Manual

Table of Contents

Advertisement

36

Wiring the fan motor: 9 lead, dual voltage, wye motor configurations

The motor wiring configurations shown below are applicable to 9 lead dual voltage wye wound motors rated for 230/460VAC and
330/600VAC. Consult the motor nameplate and/or wiring placard for verification of required wiring connections. Motors with terminal
blocks require ring terminals and a 7 mm nut driver for termination. The diagrams below include L2 and L3 swap to yield proper motor
rotation. Note: Swapping leads to reverse rotation is done only on the output side of the drive.
200–240VAC, 50–60Hz
330–350VAC, 50–60Hz
U2
T4
U5
T7
U1
T1
BLUE
RED
BLACK
GREEN W/ YELLOW
Electrical Installation (cont.)
Low Voltage
V2
W2
T5
T6
V5
W5
T8
T9
V1
W1
T2
T3
WWW.BIGASSFANS.COM
PIVOT™ 180
YELLOW
ORANGE
BROWN
GREEN W/ YELLOW
©2011 DELTA T CORP.
ALL RIGHTS RESERVED
High Voltage
400–480VAC, 50–60Hz
575–600VAC, 50–60Hz
U2
V2
W2
T4
T5
T6
U5
V5
W5
T7
T8
T9
U1
V1
W1
T1
T2
T3
Jumper bars are
provided with the
motor

Hide quick links: