4. System Controller
(b) Zone registration using the system controller (SHA-KC64AG)
In this case, you set all Central addresses by system
controller at once manually.
(1) Press the
and
for more than 4 seconds.
and CODE No. C1 will flash.
(2) After confirming that CODE No. C1 is displayed,
press the
button. Once in this mode, a change
takes place as shown in Fig. 3-38.
(3) Select the zone and group No. which you want to set
with
and
If already set, press the
(4) Set the unit No. (Indoor unit address) with
buttons, according to the zone registration table.
R.C. No. ..........................
Indoor unit No..................
(5) Press the
button.
GROUP No. turns ON and UNIT No. (Indoor unit
address) changes from flashing to ON state. UNIT
No. is registered to selected ZONE No. and GROUP
No.
If you make a mistake, then press the
reselect the ZONE, GROUP and UNIT No.
(6) Register the other UNIT Nos. in the same way by
following steps (3) to (5).
(7) Finally, complete the registration by pressing the
button.
flashes for a few minutes, then goes OFF.
(c) Automatic zone registration using the system controller
(SHA-KC64AG)
(1) Press the
and
seconds.
and CODE No. C1 will flash.
(2) Select CODE. No. C2 by pressing
and press the
button.
C2 changes from flashing to ON state and automatic zone
registration will start.
(3) All registerd GROUP Nos. will disappear.
(4) Central addresses will be assigned from small indoor unit addresses
to large addresses in numerical order automatically.
After automatic zone registration is completed,
from flashing to OFF.
(5)
If an error occurs "CHECK" starts flashing and zone
registration finishes at this time. Press the
(6) Finally, complete automatic zone registration mode by pressing the
button.
flashes for a few minutes, then goes OFF.
buttons at the same time
(GROUP) buttons.
button.
and
button
button
button and
buttons at the same time for more than 4
and
button.
3 - 57
Control of Mini ECO-i SYSTEM
If data is
registered
the unit No.
is displayed.
For example, in the case at left
Zone 3, group No. 7
Unit No. (indoor unit address) 2-8
Unit No. 2-8 is registered to zone 3-group 7.
(
) button
changes
If no data is
registered
no number
is displayed.
Selected
group No. if
no data is
registered.
Fig. 3-38
Fig. 3-39
Fig. 3-40
3