4. 1-Way Air Discharge Semi-Concealed Type (AS Type)

4-4. Noise Criterion Curves

MODEL
SOUND LEVEL : HIGH 34 dB(A), NC 25
CONDITION
SOURCE
60
50
40
30
APPROXIMATE
THRESHOLD OF
20
HEARING FOR
4
CONTINUOUS
NOISE
10
63
Frequency at center of sound pressure band (Hz)
REMARKS :
NOTE
: SPW-ASR74GX56(A/B)
-ASR94GXH56(A/B)
LOW
30 dB(A), NC 22
: Center, Under the unit 1.5 m
: 220 - 230 - 240 V, Single-phase, 50 Hz
125
250
500
1000 2000 4000 8000
1. Value obtained in the actual place where the unit is installed may be slightly higher than the values
shown in this graph because of the conditions of operation, the structure of the building, the
background noise and other factors.
2. The test results were obtained from an anechoic room.
To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read
the value at each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz
to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis.
Mini ECO-i SYSTEM Unit Specifications
MODEL
SOUND LEVEL : HIGH 38 dB(A), NC 32
CONDITION
SOURCE
60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
20
NC-20
HEARING FOR
CONTINUOUS
NOISE
10
63
Frequency at center of sound pressure band (Hz)
4 - 72
: SPW-ASR124GXH56(A/B)
LOW
31 dB(A), NC 25
: Center, Under the unit 1.5 m
: 220 - 230 - 240 V, Single-phase, 50 Hz
125
250
500
1000 2000 4000 8000
NC-50
NC-40
NC-30
NC-20