1. Main Operating Functions

1-1. Room Temperature Control

The thermostat is turned ON/OFF according to LT as shown below.
When remote controller
sensor is used
When body sensor is used
* Intake shift temperature (enabled only during heating)
During heating, a difference in temperature occurs between the top and bottom of a room. This value is set in
consideration for the difference between the temperature detected by the body sensor and the temperature at the
bottom of the room.
<Value set for intake shift temperature at time of shipment>: 4°C
Note: The shift temperature can be selected in the range of 0 – 10°C, by using the remote controller simplified
setting mode.
T
Room temperature
(deg)
+2
+1
Set temperature
–1
Thermostat
ON
(1) After the thermostat turns ON, it will not turn OFF again as a result of
(2) After the thermostat turns OFF, it will not turn ON again for 3 minutes. (It also will not turn ON for 3 minutes
after the power is switched ON.)
(3) The compressor turns OFF if the mode is changed cooling → heating (or heating → cooling) while the com-
pressor is ON.
(4) If "test run" mode is selected, the thermostat will not turn OFF as a result of
stat is forced ON.)
LT = Room temperature - Set temperature
Room temperature = Temperature detected by the remote controller sensor
Room temperature = Temperature detected by the body sensor - Intake shift temperature*
Cooling
OFF
ON
Control of Mini ECO-i SYSTEM
T
Room temperature
(deg)
+1
Set temperature
–1
–2
Thermostat
ON
L
T for 5 minutes.
L
3 - 3
Heating
OFF
ON
T for 60 minutes. (The thermo-
3