5. Schedule Timer
I Power Outages
If the air conditioner is running when power is lost, the air conditioner remains OFF when power is restored. Also, if
remote controller operation was disabled when power was lost, it is enabled for a few minutes when power is
restored.
•
Programmed operations scheduled for times that come after power is restored run as usual.
Program settings are retained in the non-volatile memory of the schedule timer, therefore they are not cleared in
•
the event of a power outage. Also, the present time and today's day of the week are retained for a maximum of
100 hours by the internal battery.
Schedule timer settings (Example)
Operation when power is not lost
Air conditioner
operation
Remote controller
operation
Operation when power is lost at 15:00 and subsequently restored
Air conditioner
operation
Remote controller
operation
8:00
Stopped
Running
Enabled
*1
*1 Whether remote controller operation is enabled or disabled depends on the setting of
the previous day.
8:00
Stopped
Running
Enabled
*1
*1 Whether remote controller operation is enabled or disabled depends on the setting of
the previous day.
*2 Remote controller operation is enabled for a few minutes after power is restored.
12:00
13:00
Stopped
Running
Disabled
Power lost here.
15:00
12:00
13:00
Stopped
Running
Disabled
3 - 77
Control of Mini ECO-i SYSTEM
17:00
18:00
20:00
Stopped
Running
Enabled
17:00
18:00
20:00
Stopped
Running
Disabled
Enabled
*2
3
Stopped
Disabled
Stopped
Disabled