3. Installation Instructions

3-1. Indoor Unit
AVOID:
G
areas where leakage of flammable gas may be
expected.
G
places where large amounts of oil mist exist.
G
direct sunlight.
G
locations near heat sources which may affect the
performance of the unit.
G
locations where external air may enter the room
directly. This may cause "sweating" on the air
discharge ports, causing them to spray or drip.
G
locations where the remote controller will be
splashed with water or affected by dampness or
humidity.
G
installing the remote controller behind curtains or
furniture.
G
locations where high-frequency emissions are
generated.
DO:
G
select an appropriate position from which every
corner of the room can be uniformly cooled.
G
select a location where the ceiling is strong enough
to support the weight of the unit.
G
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
G
allow room for operation and maintenance as well
as unrestricted air flow around the unit.
G
install the unit within the maximum elevation
difference above or below the outdoor unit and
within a total tubing length (L) from the outdoor unit
as detailed in Table 2-10.
G
allow room for mounting the remote controller about
1 m off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
NOTE
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 3 m (for LD type,
greater than 3.5 m).
Floor-Standing, Concealed Floor-Standing Type
min.
min.
10 cm
10 cm
min. 100 cm
Horizontal view
Fig. 2-4
min. 100 cm
Vertical view
2 - 25
Design of Mini ECO-i SYSTEM
Ceiling-Mounted Type
Ceiling
min. 25 cm
Front view
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
min. 50 cm
Side view
Fig. 2-1
Concealed-Duct Type
2-Way,
4-Way Semi-Concealed Type
Fig. 2-2
1-Way Semi-Concealed & Slim Type
Semi-Concealed Type
Ceiling
min. 5 cm
Wall
Obstacle
Air
discharge
Air
Wall
intake
min. 5 cm
Side view
Fig. 2-3
Wall-Mounted Type
min.
min.15 cm
15 cm
Front View
Fig. 2-5
Wall
min. 25 cm
Air intake
Max. 25 cm
Obstacle
Semi-Concealed Slim Type
100
20
cm
cm
20
cm
20
cm
100
cm
min.
15 cm
2