Zone Registration Using The System Controller (Sha-Kc64Agb); Automatic Zone Registration Using The System Controller (Sha-Kc64Agb) - Sanyo SPW-C0705DZH8 Technical Data Manual

3-way eco-i multi system 5 series
Table of Contents

Advertisement

4. System Controller
(b)

Zone registration using the system controller (SHA-KC64AGB)

In this case, you set all Central addresses by
system controller at once manually.
(1)
Press the
and
time for more than 4 seconds.
and CODE No. C1 will flash.
(2)
After confirming that CODE No. C1 is displayed,
press the
button. Once in this mode,
a change takes place as Fig. 3-52.
(3)
Select the zone and group No. which you want to
set with
buttons. If already set, press the
(4)
Set the unit No. (Indoor unit address) with
and
buttons, according to the zone
registration table.
R.C. No...........................
Indoor unit No..................
(5)
Press the
button.
1
GROUP No. turns ON and UNIT No. (Indoor unit
address) changes from flashing to ON state.
UNIT No. is registered to selected ZONE No.
and GROUP No.
If you make a mistake, then press the
and reselect the ZONE, GROUP and UNIT No.
2
(6)
Register the other UNIT Nos. in the same way by
following the steps (3) to (5).
(7)
Finally, complete the registration by pressing
the
button.
flashes for a few minutes, then goes OFF.
3
(c)
Automatic zone registration using the system
controller (SHA-KC64AGB)
4
(1)
Press the
and
time for more than 4 seconds.
and CODE No. C1 will flash.
(2)
Select CODE. No. C2 by pressing
(
) button and press the
5
C2 changes from flashing to ON state and
automatic zone registration will start.
(3) All registerd GROUP Nos. will disappear.
(4)
Central addresses will be assigned from small
indoor unit addresses to large addresses in
6
numerical order automatically.
After automatic zone registration is completed,
changes from flashing to OFF.
(5)
If an error occurs "CHECK" starts flashing and
zone registration finishes at this time.
7
Press the
button.
(6)
Finally, complete automatic zone registration
mode by pressing the
flashes for a few minutes, then goes OFF.
8
buttons at the same
and
(GROUP)
button.
button
button
buttons at the same
and
button.
button.
If data is
registered
the unit No.
is displayed.
button
For example, in the case at left
Zone 3, group No. 7
Unit No. (indoor unit address) 2-8
Unit No. 2-8 is registered to zone 3-group 7.
3-66
Control of 3-WAY ECO-i SYSTEM
If no data is
registered
no number
is displayed.
Selected
group No. if
no data is
registered.
Fig. 3-52
Fig. 3-53
Fig. 3-54