7. Remote Sensor

I How to Install the Remote Sensor

< NOTE 1 > Do not twist the remote sensor wiring with the power wiring or run
it in the same metal conduit, because this may cause malfunction.
< NOTE 2 > Install the remote sensor away from sources of electrical noise.
< NOTE 3 > Install a noise filter or take other appropriate action if electrical
noise affects the power supply circuit of the unit.
• Use an electric junction box (supplied locally) (Fig. 3-57) for flush mounting of
the remote sensor.
Simplified remote controller
Unit: mm
1. Insert a screwdriver or the like in the groove on the lower side of the remote
sensor body to pry off the back case. (Fig. 3-58)
2. Use the 2 supplied M4 machine screws to secure the remote sensor back case.
Prior to mounting, clear the cutouts in the back case corresponding to the
holes in the wall box using a screwdriver or the like. Use the spacers and take
care not to tighten the screws excessively. If the back case will not seat well,
cut the spacers to a suitable thickness.
3. Connect locally supplied 2 core lead wires to the lead wires from the remote
sensor. (See "How to wire the remote sensor.")
When connecting the locally supplied 2 core lead wires to the terminal
block, check the terminal numbers in the indoor unit to make sure that
the wires are correctly connected. (Fig. 3-59)
(The remote sensor is damaged if 220 / 240V AC is applied.)
4. Fit the remote sensor to the tabs of the back case and mount it.
Under case (back case)
Spacer
Machine screws
M4 × 25 (2)
Control of Mini ECO-i SYSTEM
Wall
Electric junction box
for one box (no cover)
Fig. 3-58
3 - 95
Fig. 3-57