TECHNICAL DATA
&
SERVICE MANUAL
SPW-XR253GH56 ⁄ SPW-CR253GHL5
SPW-XR253GH56 ⁄ SPW-CR253GL5
SPW-XR253GH56 ⁄ SPW-CR253GHL8
SPW-XR253GH56 ⁄ SPW-CR253GL8
SPW-XR363GH56 ⁄ SPW-CR363GHL8
SPW-XR363GH56 ⁄ SPW-CR363GL8
SPW-XR483GH56 ⁄ SPW-CR483GHL8
SPW-XR483GH56 ⁄ SPW-CR483GL8
SPW-UR253GHN56 ⁄ SPW-CR253GHL5
SPW-UR253GHN56 ⁄ SPW-CR253GL5
SPW-UR253GHN56 ⁄ SPW-CR253GHL8
SPW-UR253GHN56 ⁄ SPW-CR253GL8
SPW-UR363GHN56 ⁄ SPW-CR363GHL8
SPW-UR363GHN56 ⁄ SPW-CR363GL8
SPW-UR483GHN56 ⁄ SPW-CR483GHL8
SPW-UR483GHN56 ⁄ SPW-CR483GL8
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No.
SPW-XR253GH56
SPW-XR363GH56
SPW-XR483GH56
SPW-TR253GH56
SPW-TR363GH56
SPW-TR483GH56
SPW-UR253GHN56
SPW-UR363GHN56
SPW-UR483GHN56
SPW-DR253GH56
SPW-DR363GH56
SPW-DR483GH56
SPW-XR253GH56
SPW-XR363GH56
SPW-XR483GH56
SPW-UR253GHN56
SPW-UR363GHN56
SPW-UR483GHN56
85464849180000
SPW-TR253GH56 ⁄ SPW-CR253GHL5
SPW-TR253GH56 ⁄ SPW-CR253GL5
SPW-TR253GH56 ⁄ SPW-CR253GHL8
SPW-TR253GH56 ⁄ SPW-CR253GL8
SPW-TR363GH56 ⁄ SPW-CR363GHL8
SPW-TR363GH56 ⁄ SPW-CR363GL8
SPW-TR483GH56 ⁄ SPW-CR483GHL8
SPW-TR483GH56 ⁄ SPW-CR483GL8
SPW-DR253GH56 ⁄ SPW-CR253GHL5
SPW-DR253GH56 ⁄ SPW-CR253GL5
SPW-DR253GH56 ⁄ SPW-CR253GHL8
SPW-DR253GH56 ⁄ SPW-CR253GL8
SPW-DR363GH56 ⁄ SPW-CR363GHL8
SPW-DR363GH56 ⁄ SPW-CR363GL8
SPW-DR483GH56 ⁄ SPW-CR483GHL8
SPW-DR483GH56 ⁄ SPW-CR483GL8
PRODUCT CODE No.
854 014 17
854 014 18
854 014 19
854 014 31
854 014 32
854 014 33
854 015 85
854 015 86
854 015 87
854 014 34
854 014 35
854 014 36
Indoor Unit
SPW-TR253GH56
SPW-TR363GH56
SPW-TR483GH56
SPW-DR253GH56
SPW-DR363GH56
SPW-DR483GH56
FILE NO.
OUTDOOR MODEL No.
PRODUCT CODE No.
SPW-CR253GHL5
SPW-CR253GL5
SPW-CR253GHL8
SPW-CR253GL8
SPW-CR363GHL8
SPW-CR363GL8
SPW-CR483GHL8
SPW-CR483GL8
SPW-CR253GHL5, SPW-CR253GHL8
SPW-CR253GL5 , SPW-CR253GL8
SPW-CR363GHL8, SPW-CR483GHL8
SPW-CR363GL8 , SPW-CR483GL8
854 015 49
854 015 56
854 015 50
854 015 53
854 015 51
854 015 54
854 015 52
854 015 55
Outdoor Unit
SM
REFERENCE NO.
830080
Section
1
2
3
4
5

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo SPW-XR253GH56

  • Page 1 TECHNICAL DATA & FILE NO. SERVICE MANUAL SPW-XR253GH56 ⁄ SPW-CR253GHL5 SPW-TR253GH56 ⁄ SPW-CR253GHL5 SPW-XR253GH56 ⁄ SPW-CR253GL5 SPW-TR253GH56 ⁄ SPW-CR253GL5 SPW-XR253GH56 ⁄ SPW-CR253GHL8 SPW-TR253GH56 ⁄ SPW-CR253GHL8 SPW-XR253GH56 ⁄ SPW-CR253GL8 SPW-TR253GH56 ⁄ SPW-CR253GL8 SPW-XR363GH56 ⁄ SPW-CR363GHL8 SPW-TR363GH56 ⁄ SPW-CR363GHL8 SPW-XR363GH56 ⁄ SPW-CR363GL8 SPW-TR363GH56 ⁄...
  • Page 2 Important Please Read Before Starting When Installing …………………………………………………………………… …In a Room This air conditioning system meets strict safety and Properly insulate any tubing run inside a room to prevent operating standards. As the installer or service person, it “sweating” that can cause dripping and water damage to is an important part of your job to install or service the walls and floors.
  • Page 3: Table Of Contents

    WHO SHOULD USE THIS MANUAL This service manual is made to assist the service technician apply his knowledge and training to this model air conditioner. This manual is written both for experienced service persons and those who are new to air conditioning service. To help those with less experience or who are new to this kind of unit we have included more explanations of basic procedures in simple language than is usual in some service manuals.
  • Page 4 Overload Protection (Heating) ..............II - 9 Discharge Temperature Control (Cooling and Heating) ......II - 10 Auto. Mode for Automatic Heating/Cooling Switching ......II - 11 2-10 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) ....II - 12 2-11 4-Way Valve, Solenoid Control ..............II - 13 (A) Normal Control Mode ................II - 13 (B) AUTO Control Mode ................II - 14 2-12 Automatic Restart after Power Interruption ..........II - 14...
  • Page 5 Introduction: Read Me First! WHAT IS IN THIS MANUAL This manual will help you understand and service the air conditioner. To help you find the information you need, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explanations to help you find and repair problems.
  • Page 6: Specifications

    1. Specifications 1. SPECIFICATIONS Unit Specifications ................. I - 4-Way Air Discharge Semi-concealed Type ........... I - Ceiling Mounted Type ................I - 10 Concealed Duct Type ................I - 18 Concealed Duct High Static Pressure Type ..........I - 26 Major Component Specifications .............
  • Page 7: Unit Specifications

    1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-concealed Type MODEL No. Indoor Unit SPW-XR253GH56 Outdoor Unit SPW-CR253GL5 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 Hz PERFORMANCE Cooling Capacity BTU / h 25,000 Air circulation (Hi / Me / Lo)
  • Page 8 (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit Height mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) Width mm (in.)
  • Page 9 Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36 Outdoor - Hi...
  • Page 10 Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36 Outdoor - Hi...
  • Page 11 (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit Height mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) Width mm (in.)
  • Page 12 (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit Height mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) Width mm (in.)
  • Page 13 Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36 Outdoor - Hi...
  • Page 14 Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36 Outdoor - Hi...
  • Page 15 Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34 Outdoor - Hi dB - A...
  • Page 16 Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34 Outdoor - Hi dB - A...
  • Page 17 Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 42 / 40 / 35 Outdoor - Hi dB - A...
  • Page 18 Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 41 / 37 Outdoor - Hi dB - A...
  • Page 19 Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34 Outdoor - Hi dB - A...
  • Page 20 Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34 Outdoor - Hi dB - A...
  • Page 21 Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 42 / 40 / 35 Outdoor - Hi dB - A...
  • Page 22 Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (20A, OD26 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 41 / 37 Outdoor - Hi dB - A...
  • Page 23 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42 Outdoor - Hi dB - A...
  • Page 24 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42 Outdoor - Hi dB - A...
  • Page 25 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 45 / 44 / 42 Outdoor - Hi dB - A...
  • Page 26 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 47 / 46 / 44 Outdoor - Hi dB - A...
  • Page 27 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42 Outdoor - Hi dB - A...
  • Page 28 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42 Outdoor - Hi dB - A...
  • Page 29 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 45 / 44 / 42 Outdoor - Hi dB - A...
  • Page 30 Remote controller (Option) Wired : RCS-SH80TG Refrigerant control Electronic expansion valve Drain pump (Drain connection) No (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 47 / 46 / 44 Outdoor - Hi dB - A...
  • Page 31 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)
  • Page 32 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)
  • Page 33 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 38 / 33 / 31, (42 / 38 / 33 : using the booster cable)
  • Page 34 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 40 / 37 / 33, (44 / 40 / 37 : using the booster cable)
  • Page 35 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)
  • Page 36 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Rotary (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)
  • Page 37 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 38 / 33 / 31, (42 / 38 / 33 : using the booster cable)
  • Page 38 Electronic expansion valve Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm) Compressor Scroll (Sanyo) Operation sound Indoor - Hi/Me/Lo dB - A 40 / 37 / 33, (44 / 40 / 37 : using the booster cable)
  • Page 39: Major Component Specifications

    1. Specifications 1-2 Major Component Specifications (A) Indoor Units : 4-Way Air Discharge Semi-concealed Type MODEL No. SPW-XR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output...
  • Page 40 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : 4-Way Air Discharge Semi-concealed Type MODEL No. SPW-XR363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-61A3P…60 W...
  • Page 41 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : 4-Way Air Discharge Semi-concealed Type MODEL No. SPW-XR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-61A3P…60 W...
  • Page 42 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Ceiling Mounted Type MODEL No. SPW-TR253GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4 … ø 130) Fan motor Model…Nominal output SR4X-51A6P …...
  • Page 43 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Ceiling Mounted Type MODEL No. SPW-TR363GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4 … ø 150) Fan motor Model…Nominal output KFG4X-101C6P…100 W...
  • Page 44 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Ceiling Mounted Type MODEL No. SPW-TR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4…ø150) Fan motor Model…Nominal output KFG4X-101C6P…100 W Source 220 - 230 - 240 V / 1 phase / 50 Hz...
  • Page 45 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Concealed Duct High Static Pressure Type MODEL No. SPW-DR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 220) Fan motor Model…Nominal output KFC4X-201B5P …...
  • Page 46 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Concealed Duct High Static Pressure Type MODEL No. SPW-DR363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 220) Fan motor Model…Nominal output KFC4X-201B5P …...
  • Page 47 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Concealed Duct High Static Pressure Type MODEL No. SPW-DR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 250) Fan motor Model…Nominal output KFC4Q-401A5P …...
  • Page 48 1. Specifications Major Component Specifications (A) Indoor Units : Concealed Duct Type MODEL No. SPW-UR253GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 190) Fan motor Model…Nominal output KFC4X-71B5P …...
  • Page 49 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Concealed Duct Type MODEL No. SPW-UR363GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3 … ø 190) Fan motor Model…Nominal output KFC4X-141A5P…160 W...
  • Page 50 1. Specifications 1-2 Major Component Specifications (A) Indoor Units : Concealed Duct Type MODEL No. SPW-UR483GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3 … ø 190) Fan motor Model…Nominal output KFC4X-141A5P…160 W...
  • Page 51: (B) Outdoor Units

    1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR253GL5 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass'y CR - CR253GHL5 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Rotary (Hermetic) Model ..
  • Page 52 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR253GHL5 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass'y CR - CR253GHL5 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Rotary (Hermetic) Model ..
  • Page 53 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR253GL8 Source 380 - 400 - 415 V / 3 phase / 50 Hz Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Rotary (Hermetic) Model ..
  • Page 54 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR253GHL8 Source 380 - 400 - 415 V / 3 phase / 50 Hz Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Rotary (Hermetic) Model ..
  • Page 55 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR363GL8 SPW-CR483GL8 Source 380 - 400 - 415 V / 3 phase / 50 Hz Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Scroll (Hermetic) Model ..
  • Page 56 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. SPW-CR363GHL8 SPW-CR483GHL8 Source 380 - 400 - 415 V / 3 phase / 50 Hz Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor) Control circuit fuse 250 V, 3.15 A Compressor Scroll (Hermetic) Model ..
  • Page 57 20 ˚C : 6.3 ± 5 % 55 ˚C : 1.5 ± 5 % 30 ˚C : 4.0 ± 5 % Electronic expansion valve Valve body IKV-24D12 (SPW-XR253GH56) HKV-30D16 (SPW-XR363 · 483GH56) Coil DKV-MOZS582E0 (SPW-XR253GH56) EKV-MOZS584E0 (SPW-XR363 · 483GH56) Drain pump...
  • Page 58: Other Component Specifications

    1. Specifications 1-3 Other Component Specifications Ceiling Mounted Type MODEL NO. Indoor Unit SPW-TR253 ~ 483GH56 Power Transformer ATR-II215TB Rated Primary VAC, Hz 230 V, 50 Hz Secondary 10.2 V 1.4 A 14 V 0.5 A Ω Coil resistance WHT –WHT : 110 BRN –...
  • Page 59 1. Specifications 1-3 Other Component Specifications Concealed Duct High Static Pressure Type MODEL NO. Indoor Unit SPW-DR253 ~ 483GH56 Power Transformer ATR-II215TB Rated Primary VAC, Hz 230 V, 50 Hz Secondary 10.2 V 1.4 A 14 V 0.5 A Ω Coil resistance WHT –WHT : 110 BRN –...
  • Page 60 1. Specifications 1-3 Other Component Specifications Concealed Duct Type MODEL NO. Indoor Unit SPW-UR253 ~ 483GHN56 Power Transformer ATR-II215TB Rated Primary VAC, Hz 230 V, 50 Hz Secondary 10.2 V 1.4 A 14 V 0.5 A Ω Coil resistance WHT –WHT : 110 BRN –...
  • Page 61 1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL NO. Outdoor Unit SPW-CR253GL5, SPW-CR253GL8 Power Transformer ATR - I65B Rated Primary VAC, Hz 230 V, 50 Hz Secondary 14 V, 0.4 A Ω Coil resistance WHT – WHT : 300 BRN –...
  • Page 62 1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL NO. Outdoor Unit SPW-CR253GHL5, SPW-CR253GHL8 Power Transformer ATR - I65B Rated Primary VAC, Hz 230 V, 50 Hz Secondary 14 V, 0.4 A Ω Coil resistance WHT – WHT : 300 BRN –...
  • Page 63 1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL NO. Outdoor Unit SPW-CR363GL8, SPW-CR483GL8 Power Transformer ATR - I65B Rated Primary VAC, Hz 230 V, 50 Hz Secondary 14 V, 0.4 A Ω Coil resistance WHT – WHT : 300 BRN –...
  • Page 64 1. Specifications 1-3 Other Component Specifications Outdoor Unit MODEL NO. Outdoor Unit SPW-CR363GHL8 SPW-CR483GHL8 Power Transformer ATR - I65B Rated Primary VAC, Hz 230 V, 50 Hz Secondary 14 V, 0.4 A Ω Coil resistance WHT – WHT : 300 BRN –...
  • Page 65: Dimensional Data

    1. Specifications 1-4 Dimensional Data (A) Indoor Units : 4-Way Air Discharge Semi-concealed Type 25 Type 820 (Ceiling opening) 590 (Suspention bolt pitch) Air intake grille Air outlet Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line ø...
  • Page 66 1. Specifications 1-4 Dimensional Data (A) Indoor Units : 4-Way Air Discharge Semi-concealed Type 36, 48 Type 820 (Ceiling opening) 590 (Suspention bolt pitch) Air intake grille Air outlet Refrigerant liquid line (ø9.52) Refrigerant gas line (ø19.05) Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole Suspension bolt mounting...
  • Page 67 1. Specifications 1-4 Dimensional Data (A) Indoor Units : Ceiling Mounted Type 25, 36, 48 Type Holes in the rear unit (View from front) Hole for wall-through piping (View from front) C (Suspension bolt hole pitch) Air outlet or more or more Front (Service space)
  • Page 68 1. Specifications 1-4 Dimensional Data (A) Indoor Units : Concealed Duct Type 25 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (narrow tube) (Use the tube connector) Refrigerant gas line ø15.88 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
  • Page 69 1. Specifications 1-4 Dimensional Data (A) Indoor Units : Concealed Duct Type 36, 48 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (narrow tube) Refrigerant gas line ø19.05 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
  • Page 70 1. Specifications 1-4 Dimensional Data 7 Flange for the air intake duct (Field supply) : For Concealed Duct Type 260 (O.D.) 1766_U_I (mm) 200 3 × 200P = 9, 12, 18 type 698 600 170 – 180 5 × 180P = 245 (245 ×...
  • Page 71 1. Specifications 1-4 Dimensional Data (A) Indoor Units : Concealed Duct High Static Pressure Type 25, 36, 48 Type 25, 36 type 48 type Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line (ø 19.05) Power supply entry Drain connection (20 A / VP20) Duct connection for suction...
  • Page 72 1. Specifications 1-4 Dimensional Data (B) Outdoor Units : SPW-CR253GHL5 , SPW-CR253GL5 SPW-CR253GHL8 , SPW-CR253GL8 Dimension : mm Hole for anchor bolt (4-ø13) Refrigerant tube joint (narrow tube) Flare connection 1/4 in (6.35 mm) Refrigerant tube joint (wide tube) Flare connection 5/8 in (15.88 mm) Refrigerant tubing inlet Power supply inlet 0411_C_S...
  • Page 73 1. Specifications 1-4 Dimensional Data (B) Outdoor Units : SPW-CR363GHL8 , SPW-CR363GL8 SPW-CR483GHL8 , SPW-CR483GL8 Dimension : mm Hole for anchor bolt (4-ø13) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet 1553_C_S...
  • Page 74 1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Units : SPW-CR253GL5 Indoor Unit : 25 Type SPW-CR253GL8 Compressor Accumulator Accumulator High pressure Gas line switch service valve Gas line O.D. nipple ø15.88mm (5/8") Heat exchanger Heat exchanger Distributor Strainer Electronic ref.control Distributor valve Liquid line...
  • Page 75: (A) Indoor Units

    1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Units : SPW-CR363GL8 Indoor Units : 36, 48 Type SPW-CR483GL8 Low pressure switch Compressor Accumulator Gas line service High valve Gas line pressure O.D. nipple switch ø19.05mm (3/4") Heat exchanger Heat exchanger Distributor Strainer Electronic Distributor...
  • Page 76 1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Units : SPW-CR253GHL5 Indoor Unit : 25 Type SPW-CR253GHL8 Compressor Accumulator Accumulator Gas line service valve Gas line O.D. nipple ø15.88mm (5/8") High Muffler pressure switch 4-way valve Heat exchanger Heat exchanger Distributor Strainer Electronic ref.control...
  • Page 77: Operating Range

    1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Units : SPW-CR363GHL8 Indoor Units : 36, 48 Type SPW-CR483GHL8 Compressor Low pressure switch Accumulator Gas line service valve Gas line High pressure O.D. nipple switch ø19.05mm (3/4") Muffler 4-way valve Heat exchanger Heat exchanger Distributor Strainer...
  • Page 78: Cooling Capacity

    1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1140 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.22 2.37 2.55...
  • Page 79 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1140 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.07 2.22 2.38...
  • Page 80 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-XR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1920 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 10.7 10.21 9.69 9.08 8.44 2.89 3.09 3.31 3.38 3.46...
  • Page 81 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-XR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1920 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 12.71 12.13 11.52 10.8 10.03 3.42 3.66 3.93 4.14 4.38...
  • Page 82 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.22 2.37 2.55 2.49 2.45...
  • Page 83 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.22 2.37 2.55 2.49 2.45...
  • Page 84 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-TR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 10.7 10.21 9.69 9.08 8.44 2.89 3.09 3.31 3.38 3.46...
  • Page 85 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-TR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1920 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 12.71 12.13 11.52 10.8 10.03 3.42 3.66 3.93 4.14 4.38...
  • Page 86 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.35 2.51 2.69 2.63 2.58...
  • Page 87 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.35 2.52 2.55 4.86 4.68...
  • Page 88 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-UR363GHN56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 10.7 10.21 9.69 9.08 8.44 2.89 3.09 3.31 3.38 3.46...
  • Page 89 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-UR483GHN56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1980 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 12.71 12.13 11.52 10.8 10.03 3.42 3.66 3.93 4.14 4.38...
  • Page 90 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1380 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.22 2.37 2.55 2.49 2.45...
  • Page 91 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1380 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 7.37 7.03 6.67 6.26 5.81 2.07 2.22 2.38 2.49 2.62...
  • Page 92 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-DR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 10.7 10.21 9.69 9.08 8.44 2.89 3.09 3.31 3.38 3.46...
  • Page 93 1. Specifications 1-7 Cooling Capacity Indoor Unit : SPW-DR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 RATING CAPACITY : 12.6 kW AIR FLOW RATE : 2160 CMH EVAPORATOR CONDENSER ENT. TEMP. °C AMBIENT TEMP °C 12.71 12.13 11.52 10.8 10.03 3.42 3.66 3.93 4.14 4.38...
  • Page 94 1. Specifications Heating Capacity 15˚C 20˚C 25˚C 25˚C 20˚C 15˚C –15 –10 –5 Outdoor temperature ˚C WB 0413_M_S NOTE Above characteristics are based on: 1) Tubing length is 7 meters. 2) Air flow speed is high speed. Minimum outdoor ambient temperature: –15°C WB Above characteristics indicate instantaneous capacity.
  • Page 95: Noise Criterion Curves

    1. Specifications 1-8 Noise Criterion Curves 4-Way Air Discharge Semi-concealed Type MODEL : SPW-XR253GH56 MODEL : SPW-XR363GH56 , XR483GH56 SOUND LEVEL : HIGH 37 dB(A), NC 30 SOUND LEVEL : HIGH 43 dB(A), NC 36 31 dB(A), NC 22 36 dB(A), NC 24 CONDITION : Center, Under the unit 1.5 m...
  • Page 96 1. Specifications 1-8 Noise Criterion Curves Ceiling Mounted Type MODEL : SPW-TR253GH56 MODEL : SPW-TR363GH56 SOUND LEVEL : HIGH 39 dB(A), NC 34 SOUND LEVEL : HIGH 42 dB(A), NC 36 34 dB(A), NC 26 35 dB(A), NC 28 CONDITION : Distance 1 m, Under the unit 1 m CONDITION : Distance 1 m, Under the unit 1 m...
  • Page 97 1. Specifications 1-8 Noise Criterion Curves Concealed Duct Type MODEL : SPW-UR253GHN56 MODEL : SPW-UR363GHN56 SOUND LEVEL : HIGH 34 dB(A), NC 22 / LOW 27 dB(A), NC 18 SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 CONDITION : Under the unit 1.5 m CONDITION...
  • Page 98 1. Specifications 1-8 Noise Criterion Curves Concealed Duct High Static Pressure Type MODEL : SPW-DR253GH56 MODEL : SPW-DR363GH56 SOUND LEVEL : HIGH 45 dB(A), NC 39 SOUND LEVEL : HIGH 44 dB(A), NC 38 CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m SOURCE...
  • Page 99 1. Specifications 1-8 Noise Criterion Curves Outdoor Units MODEL : SPW-CR253GH5, CR253GH8 MODEL : SPW-CR363GH8 SPW-C253GH5, C253GH8 SPW-C363GH8 SOUND LEVEL : 52 dB(A), NC 44 SOUND LEVEL : 53 dB(A), NC 45 CONDITION : Distance 1m, Height 1m CONDITION : Distance 1m, Height 1m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz SOURCE...
  • Page 100 1. Specifications 1-9 Indoor Fan Performance Concealed Duct Type If external static pressure is too great (due to long Electrical component box extension of ducts, for example), the air flow volume Booster cable may drop too low at each air outlet. This problem may Booster cable be solved by increasing the fan speed using the motor...
  • Page 101: Indoor Fan Performance

    1. Specifications 1-9 Indoor Fan Performance Concealed Duct High Static Pressure Type How to Read the Diagram The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m /minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control. The name plate values are shown based on the “H”...
  • Page 102: Air Throw Distance Chart

    1. Specifications 1-10 Air throw Distance Chart 4-Way Air Discharge Semi-concealed Type Model: 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0276_X_I Model: 36, 48 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0277_X_I : LOUVER ANGLE 20˚ in Cooling mode : LOUVER ANGLE 60˚...
  • Page 103 1. Specifications 1-10 Air throw Distance Chart Ceiling Mounted Type Model: 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1225_T_I Model: 36 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1226_T_I Model: 48 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY COOLING HEATING FAN SPEED HIGH...
  • Page 104 1. Specifications 1-11 Installation Instructions Tubing Length (A) Single type Installation Example 1 Refrigerant tubing between the indoor and outdoor units should be kept as short as Tubing length (L) possible. INDOOR UNIT The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the two units.
  • Page 105: Installation Instructions

    1. Specifications 1-11 Installation Instructions Selecting the Installation Site Ceiling-Mounted Type Indoor Unit Ceiling AVOID: areas where leakage of flammable gas may be expected. Wall places where large amounts of oil mist exist. 25 cm min. 25 cm min. direct sunlight Front view NOTE NOTE...
  • Page 106 1. Specifications 1-11 Installation Instructions Selecting the Installation Site Exhaust fan Outdoor Unit Hot air Heat source AVOID: Out- heat sources, exhaust fans, etc. (Fig. 1-3) door unit damp, humid or uneven locations. 0591_C_I Fig. 1-3 choose a place as cool as possible. Table 1-2 A A A A A Dimensions choose a place that is well ventilated and outside Model...
  • Page 107 1. Specifications Air discharge 1-11 Installation Instructions Selecting the Installation Site Air Discharge Chamber for Top Discharge Be sure to install the air discharge chamber in the filed when: it is difficult to keep a space of min. 50 cm between the air discharge outlet and the obstacle.
  • Page 108 1. Specifications 1-11 Installation Instructions Selecting the Installation Site Wind Shield for “GHL”, “GL” Model Important Wind shield It is recommended to install wind shields for cooling (air discharge side) operation in low outdoor temperature condition. (Fig. 1-10) General When the outdoor unit is installed in a position ex- Front posed to strong wind (like seasonal winds with low air temperature in winter), wind shield must be installed...
  • Page 109 1. Specifications 1-11 Installation Instructions Electrical Wiring General Precautions on Wiring (7) Regulations on wire diameters differ from locality to (1) Before wiring, confirm the rated voltage of the unit locality. For field wiring rules, please refer to your as shown on its nameplate, then carry out the LOCAL ELECTRICAL CODES before beginning.
  • Page 110 1. Specifications 1-11 Installation Instructions Electrical Wiring • Indoor Unit Time Delay Power Supply Terminal Base (F) Power Supply Fuse or Type Capacity Max. Wire Circuit 2.5 mm Diameter Capacity X, S, AS, T, U, SL 245 m 15 A 50 A 14 mm (AWG#6)
  • Page 111 1. Specifications 1-11 Installation Instructions Electrical Wiring Wiring System Diagrams (1) Basic wiring diagram for standard control 1 Single type (one indoor unit) 1-1. 3-phase outdoor unit Indoor Unit Outdoor Unit R.C. Address on the PCB: 0 (S2, BLK) Inter-unit (0: Factory shipped state) power wiring (Line voltage)
  • Page 112 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz 0.6 / 0.63...
  • Page 113 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.6 / 0.63...
  • Page 114 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-XR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.92 / 0.93 1.24 / 1.31...
  • Page 115 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-XR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.92 / 0.93 1.24 / 1.31...
  • Page 116 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz 0.43 / 0.43 0.62 / 0.65...
  • Page 117 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.43 / 0.43 0.62 / 0.65...
  • Page 118 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-TR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.95 / 0.98 1.24 / 1.31...
  • Page 119 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-TR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.95 / 0.98 1.24 / 1.31...
  • Page 120 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz 0.84 / 0.9 0.62 / 0.65...
  • Page 121 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 0.84 / 0.9 0.62 / 0.65...
  • Page 122 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-UR363GHN56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 1.43 / 1.54 1.24 / 1.31...
  • Page 123 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-UR483GHN56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 1.48 / 1.58 1.24 / 1.31...
  • Page 124 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253GHL5 SPW-CR253GL5 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz 2.29 / 2.31 0.62 / 0.65...
  • Page 125 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253GHL8 SPW-CR253GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 2.29 / 2.31 0.62 / 0.65...
  • Page 126 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-DR363GH56 Outdoor Unit : SPW-CR363GHL8 SPW-CR363GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 2.46 / 2.47 1.24 / 1.31...
  • Page 127 1. Specifications 1-11 Installation Instructions Electrical Characteristics Indoor Unit : SPW-DR483GH56 Outdoor Unit : SPW-CR483GHL8 SPW-CR483GL8 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz 2.8 / 3 1.24 / 1.31...
  • Page 128 2. Processes and functions 2. PROCESSES AND FUNCTIONS Room Temperature Control ..............II - 2 (A) Cooling ....................II - 2 (B) Heating ....................II - 3 Cold Draft Prevention (Heating Cycle) ............II - 4 Automatic Fan Speed (Indoor Unit) ............II - 5 (A) Cooling ....................II - 5 (B) Heating ....................II - 5 Outdoor Fan Speed Control ..............II - 6...
  • Page 129: Processes And Functions

    2. Processes and functions 2-1 Room Temperature Control The unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the indoor unit. The figures on this and the next page show how each part of the system performs as the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF).
  • Page 130: (B) Heating

    2. Processes and functions (B) Heating THERMO. ON THERMO. ON REMOTE CONTROL THERMO. OFF THERMO. OFF SENSOR (Only for wireless THERMO. ON remote controller) SET. +1°C SETTING TEMP. SET. –1°C THERMO. OFF THERMO. OFF BODY SENSOR THERMO. ON THERMO. ON THERMO.
  • Page 131: Cold Draft Prevention (Heating Cycle)

    2. Processes and functions 2-2 Cold Draft Prevention (Heating Cycle) The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF.
  • Page 132: Automatic Fan Speed (Indoor Unit)

    2. Processes and functions 2-3 Automatic Fan Speed (Indoor Unit) By pressing the FAN SPEED button on the remote controller, the fan speed can be set at one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed will be automatically adjusted to the room temperature as the two charts shown below.
  • Page 133: Outdoor Fan Speed Control

    2. Processes and functions 2-4 Outdoor Fan Speed Control To optimize performance in air conditioner, the outdoor fan speed is selected automatically according to the outdoor temperature. Note that in both Cooling and Heating modes, the fan comes on at first at high speed (H mode) for 5 seconds.
  • Page 134: Freeze Prevention (Cooling)

    2. Processes and functions 2-5 Freeze Prevention (Cooling) Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost build up on the coil blocks cool air circulation from the indoor unit's fan. MIN.
  • Page 135: Condensing Temperature Control (Cooling)

    2. Processes and functions 2-6 Condensing Temperature Control (Cooling) Condensing temperature is controlled by the outdoor heat exchanger coil temperature as sensed by sensor C2. (°C) H or L H, L or LL ELECTRONIC CONTROL VALVE +50 step +50 step /30 sec /30 sec 1906_M_I...
  • Page 136: Overload Protection (Heating)

    2. Processes and functions 2-7 Overload Protection (Heating) This function prevents the air conditioner from overloading. (°C) INDOOR UNIT COIL TEMP. (E2) OVERLOAD PROTECTION OVERLOAD PROTECTION FUZZY CONTROL FUZZY CONTROL ELECTRONIC EXPANSION VALVE OPEN OPEN START UP OUTDOOR FM COMPENSATION H or M H or M 1565_M_S...
  • Page 137: Discharge Temperature Control (Cooling And Heating)

    2. Processes and functions 2-8 Discharge Temperature Control (Cooling and Heating) This function prevents the compressor motor from burn out by overheating. DISCHARGE GAS TEMP. (°C) OUTDOOR FAN SPEED H or M H or M COMPRESSOR ELECTRONIC EXPANSION VALVE OPEN OPEN (DISCHARGE TEMP.) TRIP IS OPERATED.
  • Page 138 2. Processes and functions 2-9 Auto. Mode for Automatic Heating/Cooling Switching COOLING SELECTION TEMP. +2.5 deg SHIFT SET TEMP. +2 deg REMOTE CONTROLLED SET TEMP. SHIFT SET TEMP. –2 deg HEATING SELECTION TEMP. –3 deg HEATING COOLING HEATING 0440_M_S Fig. 12 Chart summary and Explanations This chart shows how the Operation Mode (COOLING or HEATING) is determined by the microprocessor taking the room temperature into consideration.
  • Page 139: Defrosting Control, Outdoor Heat Exchanger Coil (Heating)

    2. Processes and functions 2-10 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) When the outdoor temperature is low, frost may form on the outdoor heat exchanger coil. When this occurred, the defrosting system operates. The microprocessor in the outdoor unit monitors the relationship between the temperature of the outdoor heat exchanger coil and the outdoor temperature so it can defrost when necessary.
  • Page 140: 4-Way Valve, Solenoid Control

    2. Processes and functions 2-11 4-Way Valve, Solenoid Control The basic function of the 4-way valve is to direct the refrigerant in the correct direction according to the Operation Mode (COOLING or HEATING) selected. The following two charts show conditions of the controls and functions listed in the left hand column when the solenoid is ON or OFF.
  • Page 141: (B) Auto Control Mode

    2. Processes and functions (B) AUTO Control Mode POWER SOURCE OPERATION BUTTON MORE THAN 10 MINUTES MORE THAN 10 MINUTES (THERMO. OFF) (THERMO. OFF) AUTO COOL COOL MODE CONTROL HEAT HEAT HEAT THERMO. OFF THERMO. ON 3 MINUTES MORE THAN 3 MINUTES COMPRESSOR MORE THAN...
  • Page 142: Electronic Expansion Control Valve

    2. Processes and functions 2-13 Electronic Expansion Valve This valve allows very precise and smooth control of the amount of refrigerant flow in the system. Since the valve is operated by a step motor, the control circuits can open or close it in very exact amounts, so the degree of heating or cooling can be changed by just a little, or changed very quickly or slowly.
  • Page 143: Compressor Current Detection Circuit

    2. Processes and functions 2-15 Compressor Current Detection Circuit The Compressor Current Detection Circuit detects the compressor current and, depending on the current range, can stop the compressor motor so it will not be damaged by overcurrent. Overcurrent can be caused by several factors, particularly mechanical seizing of the compressor or liquid backflow.
  • Page 144: Dehumidifying Operation

    2. Processes and functions 2-16 Dehumidifying Operation Dehumidifying operation uses the cooling cycle to remove moisture from the air, but by running an indoor fan at a low speed, to dehumidify without greatly lowering room temperature. In this mode, the microprocessor automatically controls the ON-OFF operation between +2 deg.
  • Page 145: Auto-Flap Control

    2. Processes and functions 2-17 Auto-flap Control (Indoor Unit : 4-Way Air Discharge Semi-Concealed Type Ceiling-Mounted Type) Auto flap can control the air flow in 5 steps. 60° Cooling F1~F3 Heating F1~F5 1328_M_I Fig. 21 Flap position Operation mode Automatic setting Optional setting Cooling/dehumidifying F1 •...
  • Page 146: Controlled By Electronic Expansion Valve

    2. Processes and functions 2-18 Controlled by Electronic Expansion Valve The circulation volume of the refrigerant is controlled by a pulse type electronic control valve. When the power is switched ON, the opening degree of the electronic control valve is controlled between 90 and 480 steps after setting the initial step at the time when the thermostat is ON.
  • Page 147: Voltage Detection Control

    2. Processes and functions 2-19 Voltage Detection Control When the power voltage falls below 160 V (voltage between N phase and each phase) or rises above 260 V, the “P2” alarm is issued to protect the compressor and electrical components. SM830080 II - 20...
  • Page 148 3. Electrical data 3. ELECTRICAL DATA Indoor Units (Electric Wiring Diagram, Schematic Diagram) ....III - 2 4-Way Air Discharge Semi-concealed Type ...........III - 2 Ceiling Mounted Type ................III - 4 Concealed Duct Type ................III - 6 Concealed Duct High Static Pressure Type ..........III - 12 Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ....
  • Page 149: Electrical Data

    3. Electrical data Indoor Units 1 1 1 1 1 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56, SPW-XR483GH56 SM830080 III - 2...
  • Page 150 3. Electrical data 3-1 Indoor Units 1 1 1 1 1 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56, SPW-XR483GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 F1(5A) 8P-1(L) 8P-R2 RC12V 8P-R3 230V 8P-2(N) 49FI Room Thermistor Indoor Coil Indoor Coil DP.DPH...
  • Page 151 3. Electrical data 3-1 Indoor Units 2 2 2 2 2 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56 SM830080 III - 4...
  • Page 152 3. Electrical data 3-1 Indoor Units 2 2 2 2 2 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 F1(5A) 8P-1(L) 8P-R2 RC12V 8P-R3 230V 8P-2(N) 49FI Room Thermistor Indoor Coil Indoor Coil Indoor Coil DC12V To Outdoor Unit Symbols...
  • Page 153 3. Electrical data 3-1 Indoor Units 3 3 3 3 3 Concealed Duct High Static Pressure Type : SPW-DR253GH56 SM830080 III - 6...
  • Page 154 3. Electrical data 3-1 Indoor Units 3 3 3 3 3 Concealed Duct High Static Pressure Type : SPW-DR253GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 F1(5A) 8P-1 8P-R2 RC12V 8P-R3 230V 8P-2 49FI Room Thermistor Indoor Coil Indoor Coil Indoor Coil Discharge Air DC12V To Outdoor Unit...
  • Page 155 3. Electrical data 3-1 Indoor Units 4 4 4 4 4 Concealed Duct High Static Pressure Type : SPW-DR363GH56 SM830080 III - 8...
  • Page 156 3. Electrical data 3-1 Indoor Units 4 4 4 4 4 Concealed Duct High Static Pressure Type : SPW-DR363GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 8P-1 F1(5A) 8P-R2 RC12V 8P-R3 230V 8P-1 49FI Room Thermistor Indoor Coil Indoor Coil Indoor Coil Discharge Air DC12V To Outdoor Unit...
  • Page 157 3. Electrical data 3-1 Indoor Units 5 5 5 5 5 Concealed Duct High Static Pressure Type : SPW-DR483GH56 SM830080 III - 10...
  • Page 158 3. Electrical data 3-1 Indoor Units 5 5 5 5 5 Concealed Duct Type : SPW-DR483GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 F0(6.3A) F1(5A) 8P-1 8P-R2 RC12V 8P-R3 230V 8P-2 49FI 3Z 2Z 1Z LL L Room Thermistor Indoor Coil Indoor Coil Indoor Coil Discharge Air...
  • Page 159 3. Electrical data 3-1 Indoor Units 6 6 6 6 6 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56 SM830080 III - 12...
  • Page 160 3. Electrical data 3-1 Indoor Units 6 6 6 6 6 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56 • Schematic Diagram CR-X253GH Controller 8P-R1 8P-1(L) F1(5A) 8P-R2 RC12V 8P-R3 230V 8P-2(N) 49FI Room Thermistor Indoor Coil Indoor Coil Indoor Coil DP.DPH Discharge Air DC12V...
  • Page 161 3. Electrical data 3-2 Outdoor Units 1 1 1 1 1 SPW-CR253GHL5, SPW-CR253GL5 SM830080 III - 14...
  • Page 162 3. Electrical data 3-2 Outdoor Units 1 1 1 1 1 SPW-CR253GHL5, SPW-CR253GL5 • Schematic Diagram Terminal CR-CR253GHL5 Plate (6P) Controller 63PH 2P-1 2P-2 L1 F1(3.15A) 63PH AC 230V ∗ AC 14V ∗ 49FO Outdoor Coil C1 Outdoor Coil C2 Discharge DC12V Symbols...
  • Page 163 3. Electrical data 3-2 Outdoor Units 2 2 2 2 2 SPW-CR253GHL8, SPW-CR253GL8 SM830080 III - 16...
  • Page 164 3. Electrical data 3-2 Outdoor Units 2 2 2 2 2 SPW-CR253GHL8, SPW-CR253GL8 • Schematic Diagram Terminal CR-CR483GHL8 Plate (8P) Controller 63PH 2P-1 2P-2 L1 F1(3.15A) 63PH AC 230V 49FO ∗ AC 14V ∗ Outdoor Coil C1 Outdoor Coil C2 Discharge DC12V N L3 L2...
  • Page 165 3. Electrical data 3-2 Outdoor Units 3 3 3 3 3 SPW-CR363GHL8, SPW-CR363GL8, SPW-CR483GHL8, SPW-CR483GL8 SM830080 III - 18...
  • Page 166 3. Electrical data 3-2 Outdoor Units 3 3 3 3 3 SPW-CR363GHL8, SPW-CR363GL8, SPW-CR483GHL8, SPW-CR483GL8 • Schematic Diagram Terminal CR-CR483GHL8 Plate (8P) Controller 63PH 2P-1 2P-2 L1 F1(3.15A) 63PH AC 230V 63PL 49FO1 ∗ AC 14V ∗ Outdoor Coil C1 49FO2 Outdoor Coil C2...
  • Page 167 4. Service procedures 4. SERVICE PROCEDURES Troubleshooting ..................IV - 2 (1) Check before and after Troubleshooting.......... IV - 3 (2) General Troubleshooting Flow Chart: Diagnosis and Remedy ..IV - 5 (3) Meanings of alarm messages ............IV - 7 (4) LED Indication on the Outdoor Unit’s P.C.B.
  • Page 168: Troubleshooting

    4. Service procedures 4-1 Troubleshooting This section explains: What the LED codes mean What the remote control unit display screen messages mean How to use the flow charts to find and solve problems How to use the self-diagnostic tests to find parts that aren’t working right This unit is made to be trouble free, and not need much service.
  • Page 169 4. Service procedures (1)-1 Check before and after Troubleshooting (SPW-CR253GHL5) Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
  • Page 170 4. Service procedures (1)-2 Check before and after Troubleshooting (SPW-CR253GHL8, CR363GHL8, CR483GHL8) Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
  • Page 171: General Troubleshooting Flow Chart: Diagnosis And Remedy

    4. Service procedures (2) General Troubleshooting Flow Chart: Diagnosis and Remedy When you have found a major problem, such as refrigerant not flowing in the system or reduced air circulation, come to this section and find the box listing the problem. Connected to the box are the main causes of the problem and their remedies.
  • Page 172 4. Service procedures (B) Heating b. Heating Poor heating Is setting temp. Change the setting temp. suitable ? Is heating load Review heating load too large ? estimate. Refrigerant flow 4-way valve is Replace the valve. failure defective. Refrigerant Charge with refrigerant.
  • Page 173: Meanings Of Alarm Messages

    4. Service procedures Meanings of alarm messages If an error occurred in the air conditioner, the error condition is presented by indicating the error code in the wired remote controller display or by the combination of lamp statuses for operation, timer and heat stand-by (OFF status and flashing status). Wired remote Wireless remote Possible causes of troubles...
  • Page 174 4. Service procedures Wired remote Wireless remote Possible causes of troubles controller controller display display Operation lamp Indoor thermistor is either Indoor coil temp. (E1 = TH2) cannot be detected. and heat stand-by open or short. Indoor coil temp. (E2 = TH3) cannot be detected. lamp flash alternately.
  • Page 175: Led Indication On The Outdoor Unit's P.c.b. Ass'y

    4. Service procedures (4) LED Indication on the Outdoor Unit’s P.C.B. Ass’y If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Ass’y light up to show the cause of the trouble, in addition to the Alarm message on the remote controller.
  • Page 176: Symptoms And Parts To Inspect

    4. Service procedures Symptoms and parts to inspect Symptom: LCD on the remote controller does not display and remote controller does not operate. Start Is the LED (D80) on the indoor unit PCB lit? Is there 12 V DC Is there 12 V DC Repair the between R2 and R3 between 2 and 3...
  • Page 177 4. Service procedures 2) Symptom: LCD on the remote controller displays “CHECK E01”. (Unusual communication between remote controller and indoor unit.) Start Remote controller judges itself Replace the remote controller. with self-diagnostic functions Is there an open or a contact defect in the No.
  • Page 178 4. Service procedures Symptom: LCD on the remote controller is displaying “CHECK E04”. (Unusual communication between the indoor and outdoor units.) Start Cut the breaker and remove the Is the contact good at the 2P Correct the connections. indoor/outdoor unit control lines connector for indoor serial connected to U1 and U2 of the communications on the outdoor...
  • Page 179 4. Service procedures Symptom: LCD on the remote controller is displaying “CHECK E06”. (Unusual communication between the indoor and outdoor units) Start Is there a cut line or contact Correct wiring. defect between an indoor and outdoor unit’s control line? 1903_M_I Influenced by external noise * See the section of INSTALLATION INSTRUCTION concerning with flexible...
  • Page 180 4. Service procedures Symptom: LCD on the remote controller displays “CHECK P01”. (Indoor fan protection thermostat operation warning) Start Is there 220-240 V AC between S4 and T20-3 on the indoor unit PCB? Correct the connection Is there 220-240 V AC between Is the indoor fan wire winding T20-3 and S4 after T20-1 and T20-3 protection thermostat (49FI) off?
  • Page 181 4. Service procedures 10) Symptom: LCD on the remote controller displays “CHECK P02”. (Compressor / outdoor fan protection thermostat operation warning / power supply voltage abnormality) Start Is the power supply to the outdoor Check the power breaker etc. unit normal? and repair.
  • Page 182 4. Service procedures 11) Symptoms: LCD on the remote controller displays “CHECK P03”. (Alarm for unusual discharge temp. of compressor) Start Unusual discharge gas temperature • Refrigerant shortage • Clogged refrigerant circuit • Electronic refrigerant control valve defect (indoor unit) 0343_M_I 12) Symptom: LCD on the remote controller displays “CHECK P04”.
  • Page 183 4. Service procedures 13) Symptom: LCD on the remote controller displays “CHECK P05”. (Negative phase detection operation warning) Start Is the power supply to the outdoor Check the power breaker etc. unit normal? and repair (Voltage defective phase?) Does the outdoor unit operate when No problem two of the three phases are changed? (Actuation of negative phase protector)
  • Page 184 4. Service procedures 15) Symptom: LCD on the remote controller displays “CHECK E16”. Start When the group of the units are Repair the wiring. installed, is there any mis-cross between inter unit control wiring and refrigerant tubing? Are the total capacities of indoor units Select indoor units which match with to that of outdoor units more than 107%? the outdoor capacity.
  • Page 185 4. Service procedures 17) Symptom: LCD on the remote controller displays “CHECK H01, H02, H03”. (PC compressor current detection) * Please check the related part described in the following chart after confirming the code setting (S4) of the outdoor unit’s capacity on the PCB in the outdoor unit. Start “CHECK H01”...
  • Page 186: Indoor Unit (Electric Wiring Diagram, Schematic Diagram)

    4. Service procedures Procedures When a Specific Component Does Not Work Indoor fan does not operate. Is fan motor capacitor Replace the capacitor. normal ? Is there voltage output Replace the P.C.B. Ass'y of P.C.B. Ass'y for fan in the indoor unit. motor ? •...
  • Page 187 4. Service procedures Compressor motor does not operate. Does compressor motor magnetic Replace the compressor contactor (52C) actuate ? motor magnetic contactor. Check resistance of compressor motor winding. Replace the compressor. 0461_M_I Outdoor fan does not operate. Are auxiliary relays (1Y, 2Y) Replace the relays.
  • Page 188: Service Functions Of Remote Controller

    4. Service procedures Service Functions of Remote Controller From the remote controller you can control both the operation and settings of the unit as well as perform several useful service checks. This section explains how to use the remote controller on the following items from (A) to (J). (A) Set service check switches.
  • Page 189 4. Service procedures (B) Use the test run procedure The purpose of the test run function is to let you control the operation of the unit directly without turning the unit on or off by thermostat. As indicated in the following procedure, be sure to stop test run operation when you finish the procedure, or the air conditioner may be damaged.
  • Page 190 4. Service procedures (C) Check the sensor temperature readings The air conditioner has thermo sensors which are used to control the unit. Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor unit address is used only when several units are hooked up to one remote controller (group control).
  • Page 191 4. Service procedures Refer to the table below for the relationship between the sensor address and the location of the sensor. Relationship between the sensor address and the location of sensor Sensor Address Location of Sensor (Themistor): ˚C (CODE No.) Indoor Unit —...
  • Page 192 4. Service procedures This picture shows the service check display. UNIT No. UNIT No. 1–1 R.C. CODE Refrigerant Circuit No. CODE No. CHECK Alarm message SERVICE 0358_M_I c. A maximum of 4 alarm messages can be accessed by pressing either SET TEMP button as follows.
  • Page 193 4. Service procedures Important Never press CL (clear) button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. To erase accessed data, press the CL button. When erasing is finished,“----” mark appears on the controller’s display. CAUTION After checking the alarm messages, be sure to press the TEST / CHK button.
  • Page 194 4. Service procedures (F) Execute the auto. address operation Auto. address operation is executed by pressing the A. ADD (S1) button of outdoor unit’s PCB usually. For your convenience it can be executed by remote controller also. a Press the TEST / CHK and ) buttons at the same time for more than 4 seconds.
  • Page 195 4. Service procedures (G) Confirm and change the indoor unit address The purpose of the above function is to let you confirm the indoor unit address after the auto. address operation, and change the indoor unit address if it is needed.
  • Page 196 4. Service procedures e Set the required new indoor unit’s No. by pressing the ) button. AIR FLOW UNIT MODE Ex: UNIT No. 3-6: currently registered indoor unit address R.C. FLAP SET TEMP. CODE TIMER SET FAN SPEED SETTING DATA Required new indoor No.8: SET DATA In this case, UNIT No.
  • Page 197 4. Service procedures (H) Change the shift temperature in heating mode If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off at heating mode because of the hot air temperature around ceiling level. In order to solve the problem, the shift temp.
  • Page 198 4. Service procedures ( I ) Set the indoor unit address This function is usable if the auto. address operation is not available. Indoor unit address can be set one by one by remote controller. NOTE 1) In case of group control, branch wiring for group control should be removed temporarily.
  • Page 199 4. Service procedures d Set the No. of R. C. which you want to set with ) button. Ex. No. of R. C. will be set 2. AIR FLOW UNIT MODE UNIT No. R.C. FLAP SET TEMP. CODE TIMER SET FAN SPEED SETTING DATA...
  • Page 200 4. Service procedures i Select the code No. 14 to set group setting with the (SET TEMP) button. j Set the No. of group setting as shown below with the ) button. Nos. of group setting. AIR FLOW 0 : Standard system (except group UNIT MODE UNIT No.
  • Page 201 4. Service procedures (J) Change the period of the filter timer If the period of filter timer is not suitable (for example in case of dirty environment), the period can be shortened to half as follows: a Press the TEST / CHK button for more than 4 seconds. AIR FLOW UNIT MODE...
  • Page 202: Outdoor Unit (Electric Wiring Diagram, Schematic Diagram)

    4. Service procedures 4-2 Checking the Electrical Components Measurement of Insulation Resistance • The insulation is in good condition if the resistance exceeds 1 MΩ. Power Supply Wires Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resis- Earthed wire tance tester and measure the resistance by placing a probe on either of the power wires.
  • Page 203: Measurement Of Insulation Resistance For Electrical Parts

    4. Service procedures Measurement of Insulation Resistance for Electrical parts Probe • Disconnect the connector of the desired electric part from terminal plate, P.C.B. Ass’y, etc. (Fig. 27) • Similary, disconnect the lead wires from Clip compressor, capacitor, etc. (Fig. 28) Copper tube or •...
  • Page 204: Checking The Protective Devices

    4. Service procedures Checking the Protective Devices • Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device. • Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 29. •...
  • Page 205: Checking The Electrical Parts

    4. Service procedures Checking the Electrical Parts Power transformer (TR1) ....Indoor unit *Measure the coil resistance. • Primary ; Measure the resistance between No.1 and No.3 (WHT lead wires) terminals of 3P (WHT) socket connected to power transformer. • Secondary 14V ;...
  • Page 206 4. Service procedures Solenoid coil of the electronic refrigerant *Measure the coil resistance. control valve (ERCV) ………… Indoor unit • Measure the resistance between No. 5 (GRY lead wire) and other terminals (another color of lead wires) of 5P (WHT) plug connected to the solenoid coil. Refer to “1-2-(A) Major component specifications”.
  • Page 207 4. Service procedures Fuse on indoor and outdoor P.C.B. Ass’y …. Both in indoor and outdoor unit *Check the continuity. • Remove the P.C.B. Ass’y from the electrical component box. Then pull out the fuse from the P.C.B. Ass’y. (Fig. 31) Fuses Fuses Indoor P.C.B.
  • Page 208: Sensor And Solenoid Layout Diagram

    4. Service procedures Sensor and Solenoid Layout Diagram Indoor Unit • SPW-XR363GH56 • SPW-XR253GH56 • SPW-XR483GH56 Electronic expansion valve Electronic expansion valve (E1), (RED) TH2 (E1), (RED) TH3 (E2), (BLK) (E3), (BRN) TH3 (E2), (BLK) TH4 (E3), (BRN) 1251_X_I 1250_X_I...
  • Page 209 4. Service procedures Indoor Unit • SPW-TR253GH56 TH3 (E2), (BLK) TH4 (E3), (BRN) TH2 (E1), (RED) Electronic expansion valve 1218_THS_I • SPW-TR363GH56, SPW-TR483GH56 TH3 (E2), (BLK) TH2 (E1), (RED) Electronic expansion valve TH4 (E3), (BRN) 1219_THS_I SM830080 IV - 43...
  • Page 210 4. Service procedures Indoor Unit • SPW-DR253GH56 • SPW-DR363GH56 • SPW-DR483GH56 Electronic expansion valve Electronic expansion valve TH2 (E1), (RED) TH4 (E3), (BRN) TH4 (E3), (BRN) TH3 (E2), (BLK) TH3 (E2), (BLK) 1256_D_I TH2 (E1), (RED) 1255_D_I TH5 (GRN), (Discharge Air) Fan motor 1263_C_I •...
  • Page 211 4. Service procedures Outdoor Units • SPW-CR253GHL5, SPW-CR253GHL8 TH6, 7, 8 20S, 63PH TH8 (GRN) TH7 (C2), (RED) ( Discharge gas) TH6 (C1), (BLK) 0582_C_S 0583_C_S • SPW-CR363GHL8 TH6, 7, 8 TH7 (C2), (RED) 63PH TH8 (GRN) ( Discharge gas) TH6 (C1), (BLK) 0585_C_S 0584_C_S...
  • Page 212 4. Service procedures Outdoor Units • SPW-CR483GHL8 TH6, 7, 8 TH7 (C2), (RED) 63PH TH8 (GRN) ( Discharge gas) TH6 (C1), (BLK) 0585_C_S 0586_C_S SM830080 IV - 46...
  • Page 213: Thermistor Characteristic Curve

    4. Service procedures (6) Thermistor Characteristic Curve (1) Room temp. sensor : TH1 (KTEC-35) (2) Indoor heat exch. TH5 (KTEC-35) coil sensor : TH2(E1), TH3(E2), TH4(E3) Outdoor heat exch. coil sensor : TH6(C1), TH7(C2) ( PBC-41E) ( PB3M-41E) –20 –15 –10 –5 Temperature (°C)
  • Page 214: Setting

    4. Service procedures (7) P.C.B. Setting Setting of outdoor control PCB (A) Standard control (single outdoor unit) In case of single outdoor unit installation, even if in case of twin, triple or quartet type (2, 3 or 4 indoor units), no setting necessary. Keep factory shipment state (R.C.
  • Page 215: Address Setting Method

    4. Service procedures (8) R.C. Address Setting Method Outdoor unit R.C. address setting method In case of group control or central control, set the R.C. address to 1, 2, 3, ... according to the No. of outdoor units. Outdoor control PCB CN4 (2P Black) Refrigerant circuit address (factory setting = 0)
  • Page 216: Automatic Address Setting Method

    4. Service procedures (9) Automatic Address Setting Method 7 Complete the auto. address op- eration by pressing the TEST / — For group control and central control with CHK button. multiple outdoor units — NOTE Carry out automatic address setting with Required time for auto.
  • Page 217: Items To Check Prior To Test Run

    4. Service procedures (11) Items to Check Prior to Test Run (1) Turn on the power supply switch more than 5 hours before in order to charge the crank case heater. (2) Fully open the outdoor service valve after making the leak inspection of field connected tubing, vacuuming, and gas charging if necessary.
  • Page 218: Test Run Procedure

    4. Service procedures (12) Test Run Procedure Start Turn on RCU address SW Multiple remote of sub remote control unit control? Recheck the test items before test operation. Check the indoor and outdoor unit combination (wiring). Single type? Multiple indoor (One indoor unit and one units for one outdoor remote controller for one...
  • Page 219: Appendix

    5. Appendix 5. APPENDIX P.C.B...................... V - 2 SM830080 V - 1...
  • Page 220 5. Appendix 5-1 P.C.B. Outdoor Unit Control P.C.B. : SPW-CR253GHL8 , SPW-CR363GHL8 , SPW-CR483GHL8 SPW-CR253GL8 , SPW-CR363GL8 , SPW-CR483GL8 CN9 : CK.H CN8 CK.L CN15 (GRN) : DISCH CN7 (RED) : CHECK CN14 (RED) : C2 CN13 (BLK) : C1 (Used for Heatpump Type only) CN11 (YEL) : TEST CN1 : VCC...
  • Page 221 5. Appendix 5-1 P.C.B. Outdoor Unit Control P.C.B. : SPW-CR253GHL5 , SPW-CR253GL5 CN9 : CK.H CN8 CK.L CN15 (GRN) : DISCH CN7 (RED) : CHECK CN14 (RED) : C2 CN13 (BLK) : C1 (Used for Heatpump Type only) CN11 (YEL) : TEST CN1 : VCC JP11 CN10...
  • Page 222 5. Appendix 5-1 P.C.B. Indoor Unit Control P.C.B. (CR-X253GH) CN79 (RED) : HU1 CN77 (GRN) : LM CN85 (BLU) : DPH CN74 (WHT) : RN2 CN76 (BLK) : OP1 CN73 (BLK) : RN1 CN78 (BLU) : DP CN84 (WHT) : RN3 F1 : Fuse 250V / 5A CN81 (GRY) : T20 CN80 (RED) : 26H...
  • Page 223 • The specifications, designs, and information in this brochure are subject to change without notice. SANYO Electric Air Conditioning Co., Ltd. Tochigi, Japan G1100 G 500 Printed in Japan...