How To Perform Zone Registration - Sanyo C4272R S/C Installation Instructions Manual

Sanyo split system heat pump air conditioner installation instructions
Table of Contents

Advertisement

07-115 SSHP_II
5/7/07
4:00 PM

8-5. How to Perform Zone Registration

To operate the system controller properly, zone registration is required after finishing the test run (and after
setting all indoor unit addresses) using one of the following methods.
(a) Zone registration using the remote controller (RCS-SH80UG)
Refer to page 91.
(b) Zone registration using the system controller (SHA-KC64UG)
Refer to page 92.
(c) Automatic zone registration using the system controller (SHA-KC64UG)
Refer to page 93.
For methods (a) and (b), you should make a zone registration table manually before performing the
registration as shown on the next page.
For method (c), zone registration is executed automatically, proceeding from the smallest indoor unit address and
smallest central addresses to larger numbers in numerical order. For example:
Central address
ZONE–group
Indoor unit address
NOTE
1.
An indoor unit address is assigned to each indoor unit during automatic address
operation. Each indoor unit address combines an R.C. address and indoor unit number
as follows:
This address is displayed on the remote controller for UNIT No. when the UNIT
2.
button is pressed.
The central address represents the zone and group number. These addresses are
assigned in ascending numerical order.
SC
Page 90
1
2
3
4
1-1
1-2
1-3
1-4
1-1
1-2
2-1
2-2
1 – 1
: Indoor unit address (UNIT No.)
Indoor unit No.
Refrigerant circuit No. (R.C. address)
5
6
1-5
1-6
2-3
3-1
90