2. Wireless Remote Controller

I RCS-TH80AG.WL for 2-Way Type (S Type)

For 2-Way Cassette Type (S Type)

2-12. Installing the Display

G
Remove panel cover A and install the display.
(1) Remove cover A from the rear side of the panel.
(2) Cover B is fit inside cover A. Therefore, spread
cover A and remove cover B, as shown in
Fig. 3-17.
Remove the tape that holds cover B in place. It
was used for protection during shipping.
(3) Fit the display into the panel.
(4) Pass the display lead wire through the notch in the
panel. Use the hole in the plate and a clamp to
fasten the wire in place.
(5) Reattach cover A.
3

2-13. Installing the Control Unit

NOTE
G
Do not twist the control wiring with the power wiring
because this may cause malfunction.
G
Install a noise filter or take other appropriate action
if electrical noise affects the power supply circuit of
the unit.
(1) Use the 2 supplied screws (4 x 10) to attach the
control unit at the location shown in the diagram
below.
(2) Connect the display and control unit 6P connec-
tors.
(3) Connect the control unit lead wire to the indoor
unit remote controller wiring terminal.
(4) Bend the lead wire into the correct shape, and use
a figure 8 clamp to fasten it in place.
(5) Attach the ceiling panel.
* For the wiring and test run procedures, refer to
"Wiring the Receiver Unit" and "Test Run."
Control of Mini ECO-i SYSTEM
Cover B
Spread
Fasten the wire in the hole of the plate.
Pass the display lead
wire through the
notch in the panel.
Bend the excess lead wire,
then use the figure 8 clamp to fasten it in place.
3 - 16
Cover A
Display
Fig. 3-17
Fig. 3-18
Control unit
Fig. 3-19