INSTALLATION
M6
12 Hex Bolts
(3 places)
Terminal Block
Assembly Bracket
10
Eaton BladeUPS Bar Installation Guide
12. Secure the bar to the wireway with three M6 12 hex bolts. Install
the bolts from the front of the rack. See Figure 5. Torque the bolts
to 5.1 ± 0.8 Nm (45 ± 7 lb in).
13. Reinstall the terminal block assembly bracket removed in Step 10.
Install the bolts from the front of the rack. See Figure 5. Torque the
bolts to 5.1 ± 0.8 Nm (45 ± 7 lb in).
NOTE Do not change the original orientation of the terminal block assembly bracket. Verify
that the threaded holes mount to the rack, not to the bar.
Figure 5. Terminal Block Assembly Installation
S
164201723 Rev 2 www.eaton.com/powerquality
Front of Rack
Rear of Rack