Eaton BladeUPS Installation Manual page 13

Eaton powerware series bladeups bar installation guide
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Front of Rack
M6 Hex Nuts on
Wireway Studs
(3 places)
Ferrite Assembly (secured to
wireway floor with tie wrap)
Eaton BladeUPS Bar Installation Guide
9.
Place the ferrite assembly on the floor of the wireway and secure
with the supplied tie wrap. Loop the tie wrap through both
attachment sites on the wireway floor and through the ferrite
assembly. See Figure 4.
10. Note the orientation of the terminal block assembly bracket installed
on the bar for later re-installation (see Figure 5). Remove and retain
the terminal block assembly bracket and hardware.
11. Place the bar in the rack as shown in Figure 4.
NOTE The bar can rest on the floor of the rack until secured in place. After complete
installation, the bar will be secured to the rack and wireway as shown in Figure 4.
Figure 4. Ferrite and Bar Placement
NOTE Verify that the bar is secure as shown in Figure 4. The sheetmetal at the top and
bottom of the of the terminal block assembly should fit between the wireway tabs.
OUTPUT
A
INPUT
OUTPUT
A
B
INPUT
OUTPUT
B
C
INPUT
C
NEUTRAL
S
164201723 Rev 2 www.eaton.com/powerquality
INSTALLATION
Bar
Wireway Tabs
Rear of Rack
9