Table Of Commands - Omron C200H-TV Series Operation Manual

Heat/cool temperature control unit
Hide thumbs Also See for C200H-TV Series:
Table of Contents

Advertisement

Memory Allocation
I/O
Address
Word
Input
n+6
n+7
n+8 Loop 1
n+9 Loop 2
9 L
2

4-1-3 Table of Commands

Parameter
Set point
Executed bank number
Data item
Bit
07 to 01
---
00
Read
complete
15 to 12
Loop 1
executed
bank
number
11 to 08
Loop 2
executed
bank
number
07 to 02
---
01
SW2-2
00
SW2-1
15
---
14
Sensor
error
13
CT
overflow
12 to 09
---
08
RUN
07 and 06
---
05
Cooling
control
output
04
Heating
control
output
03
AT
02
HB
01
AL1
00
AL2
The command codes shown below are set in bits (n Wd) 07 to 00 when the
SW2-1 (switching memory contents) on the front panel is set in the Normal posi-
tion.
Com-
Write
Read
mand
0
0
Yes
Yes
0
2
Yes
Yes
Data contents
Not used. Each bit is set to 0.
Bit set to 1 when the read operation executed by means of the
command set with Wd (n) ends normally. The bit is automatically
set to 0 when the next command is set.
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
Not used. Set to 0.
Bit set to 1 if the sensor is not connected, a sensor
wire is broken, or the input data exceeds the
operational temperature range.
Bit set to 1 when the detected heater current
exceeds 55.0 A.
Not used. Each bit is set to 0.
Bit set to 1 during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or
voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Bit set to 1 if the detected heater current drops
below the set heater burnout current value. (HB:
heater burnout)
Bit set to 1 when the temperature enters the set
alarm range (Refer to page 23).
l
(R f
t
Loop
Bank
Actual data
no.
no.
range
Yes
Yes
SV lower limit to SV upper
limit
Yes
No
1 to 8
Section 4-1
23)
Write/Read
Default value
data range
0 C
0001 to
1
0008
Loop 1/2
status data
t t
d t
41