General Specifications
Conforms to the C200H PC specifications.
Item
Connectable temperature
sensor (see note 1)
Current Transformer detection
current
No. of input points (loops)
Temperature control mode
Setting/designation accuracy
(See notes 2 and 3.)
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
Output refresh period
Display refresh period
Input shift range
Alarm output setting range
No. of banks
Internal current consumption
External supply voltage
Dimensions (see note 4)
Weight
Note 1. Set with the switch on the rear panel. See Appendix B Sensor Temperature Measurement Range for the
measurable temperature range.
2. The set value and designated value coincide with each other.
3. The indication accuracy of thermocouples R and S at a temperature of 200 C max., that of thermocou-
ples K and T at a temperature of –100 C max, and that of thermocouple U are all 4 C, 1 digit max. The
indication accuracy of thermocouple B at a temperature of 400 C or below is not guaranteed.
4. See Appendix D Dimensions .
Appendix A
Specifications
C200H-TV00
Thermocouple (R, S, K, J, T, E, B, N, L, U) Platinum resistance thermometer (JPt100,
0.1 to 49.9 A (with a heater burnout detecting current difference of 2.5 A min.)
Indication accuracy: 5% FS 1 digit max.
Two points (two loops, each of which consists of a temperature sensor and a CT)
PID, ON/OFF (selectable with a switch on the rear panel)
(advanced PID control with auto-tuning)
0.5% of set (designated) value or 2 C
(whichever is larger) 1 digit max.
0.0 to 999.9 C/ F (in units of 0.1 C/ F) (during ON/OFF control action)
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
0 to 9999 s (in units of 1 s)
0 to 9999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
500 ms
500 ms
500 ms
–99.9 to 999.9 C/ F (in units of 0.1 C/ F)
–999 to 9,999 C/ F (in units of 1 C/ F)
8 banks
5 VDC, 0.33 A max.
+10%
24 VDC
/
, 0.2 A min.
–15%
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
360 g
C200H-TV10
Pt100)
0.5% of set (designated) value or 1 C
(whichever is larger) 1 digit max.
–99.9 to 999.9 C/ F (in units of 0.1 C/ F)
57