SECTION 5 Modbus Communications Procedure

■ Operation Commands

5-14
This function performs commands such as communications writing,
run/stop, multi-SP, AT (auto-tuning) execute/cancel, write mode, save
RAM data, software reset, move to setup area 1, move to protect level,
auto/manual mode, initialize settings, clear alarm latch, and program
start.
Command Frame
Slave
Function
Write
address
code
start address
H'06
H'00
H'00
1
1
2
Response Frame
Slave
Function
Write
address
code
start address
H'06
H'00
H'00
1
1
2
(1) Command Code and Related Information
Command
Command content
code
00
Communications writ-
ing
01
RUN/STOP
02
Multi-SP
03
AT execute/cancel
04
Write mode
05
Save RAM data
06
Software reset
07
Move to setup area 1
08
Move to protect level
09
Auto/manual switch
0B
Parameter initialization
11
Program start
* No response will be returned when a software reset is carried out.
Write data
CRC-16
2
2 bytes
CRC-16
Write data
2
2 bytes
Related information
00: OFF (disabled)
01: ON (enabled)
00: Run
01: Stop
00: Set point 0
01: Set point 1
02: Set point 2
03: Set point 3
00: Cancel
01: AT execute
00: Backup
01: RAM
00
00
00
00
00: Automatic mode
01: Manual mode
00: Initialize to defaults
01: Initial settings service values
00: Reset
01: Start