Switch Settings - Omron C200H-TV Series Operation Manual

Heat/cool temperature control unit
Hide thumbs Also See for C200H-TV Series:
Table of Contents

Advertisement

Switch Settings

Indicators
2-2

Switch Settings

Unit Number
Switching Memory Contents and Setting Direction
RUN
Lit when the Heat/Cool Temperature Control Unit is operating normally.
Unlit when an alarm occurs, and Unit operation stops.
The function and setting of switches are identical for all models, except SW202.
SW1
4
(3)
2
(1)
0
(5)
(9)
8
(7)
6
The addresses are allocated as shown in the following table according to the
Unit number setting.
Unit no.
setting
0
Wd 100 to 109
1
Wd 110 to 119
2
Wd 120 to 129
3
Wd 130 to 139
4
Wd 140 to 149
5
Wd 150 to 159
6
Wd 160 to 169
7
Wd 170 to 179
8
Wd 180 to 189
9
Wd 190 to 199
The switch is factory-set to 0.
Note If the Unit number is set to an existing Unit number, an alarm occurs and the
C200H does not operate.
Turn the C200H power off before setting the Unit number. If the setting is
changed with the power on, the new setting is not valid until the power is turned
off and back on again.
SW2
Remove the cover and set the switch with the tip of a ballpoint pen or a similar
object.
Unit number setting
The cut-out indicates the selected position. Negative numbers
are not indicated. Turn the switch with a flat-blade screwdriver.
Turn the switch until it clicks in position. Do not leave the switch
between two settings.
Allocated address
Switching memory contents and setting direction
ON
OFF
Section 2-2
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents