Omron C200H-TV Series Operation Manual page 36

Heat/cool temperature control unit
Hide thumbs Also See for C200H-TV Series:
Table of Contents

Advertisement

Parameter Displays and Settings
Alarm 1 and Alarm 2 Modes (Display Level 2)
32
PV
SV
PV
SV
Select the desired alarm type from the following chart and set the number (X: set
value)
Alarm
Alarm Type
Mode
0
No alarm
1
Upper- and lower-limit alarm
2
Upper-limit alarm
3
Lower-limit alarm
4
Upper- and lower-limit range alarm
5
Upper- and lower-limit alarm with
standby sequence
6
Upper-limit alarm with standby
sequence
7
Lower-limit alarm with standby
sequence
8
Absolute-value upper-limit alarm
9
Absolute-value lower-limit alarm
Standby Sequence
When the power is turned on, the temperature is below the set point, so alarm
output status occurs with regard to the lower limit alarm. In this situation, if "lower
limit alarm with standby sequence" is selected, the standby sequence recog-
nizes that the value is out of the alarm range and then outputs an alarm when the
value enters the alarm range once more.
Alarm 1 Mode parameter symbol
Alarm 1 Mode of currently selected loop
Alarm 2 Mode parameter symbol
Alarm 2 Mode of currently selected loop
Alarm Range
0
x
x
x
x
x
x
Section 3-4
SP
x
x
x
x
x
x