Parameter Displays and Settings
SP Lower Limit (Display Level 1)
SP Upper Limit (Display Level 1)
Dead Band (Display Level 1)
28
This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID
control).
This value is reflected even when auto-tuning (AT) is executed.
PV
SV
Settings can be made within the following range:
Sensor measuring range lower limit to (SP upper limit – 1 digit)
When powering up or starting, the lower limit of the measuring range for sen-
sors set by the rear-panel SW202 (sensor type) is set automatically. For exam-
ple, if SW202 is set to "2," the thermocouple type is set to "–200." However, the
SP lower limit will not be changed if the current SV lies inside the sensor mea-
suring range.
PV
SV
Settings can be made within the following range:
(SP limit + 1 digit) to sensor measuring range upper limit
When powering up or starting, the upper limit of the measuring range for sen-
sors set by the rear-panel SW202 (sensor type) is set automatically. For exam-
ple, if SW202 is set to "2," the thermocouple type is set to "1300." However, the
SP upper limit will not be changed if the current SV lies inside the sensor mea-
suring range.
PV
SV
This sets the cooling output dead band, and it is valid when SW203-1 (PID con-
trol) is OFF.
The relation between the dead band and the set temperature is as shown in the
illustration below.
Output volume
Heating output
100%
0%
SP lower limit parameter symbol
SP lower limit of currently selected loop
(unit: C or F)
SP upper limit parameter symbol
SP upper limit of currently selected loop
(unit: C or F)
Dead band parameter symbol
Dead band of currently selected loop (unit: C or F)
Dead band
Set value
Section 3-4
Cooling output
Temperature