Parameter Displays and Settings
Alarm SV 1 (Display Level 0)
Alarm SV 2 (Display Level 0)
Input Shift Value (Display Level 0)
Proportional Band (Display Level 0)
Integral (Reset) Time (Display Level 0)
Derivative (Rate) Time (Display Level 0)
When changing these parameters from the Data Setting Console, stop opera-
tion. While operation is stopped, the bank number setting can be changed.
PV
SV
Not valid when Alarm mode = 0.
PV
SV
Not valid when Alarm mode = 0.
PV
SV
If the displayed temperature value differs from the actual temperature value due
to the sensor position or some other conditions, set the input shift value such that
the correct temperature is displayed.
PV
SV
This sets the proportional band. It is valid only when SW203-1 is set to OFF
(i.e., PID control).
This value is reflected even when auto-tuning (AT) is executed.
If this value is set to "0.0," ON/OFF control is executed.
PV
SV
This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID
control).
This value is reflected even when auto-tuning (AT) is executed.
PV
SV
Alarm 1 parameter symbol
Alarm SV of currently selected bank and loop (unit: C or F)
Alarm 2 parameter symbol
Alarm SV of currently selected bank and loop (unit: C or F)
Input shift value parameter symbol
Input shift value of currently selected bank and loop (unit:
C or F)
Proportional band parameter symbol
Proportional band of currently selected bank and loop
(unit: C or F)
Integral time parameter symbol
Integral time of currently selected bank and loop (unit: se-
cond)
Derivative time parameter symbol
Derivative time of currently selected bank and loop
(unit: second)
Section 3-4
27