Omron C200H-TV Series Operation Manual page 42

Heat/cool temperature control unit
Hide thumbs Also See for C200H-TV Series:
Table of Contents

Advertisement

Memory Allocation
I/O
Address
Word
Input
n+3
n+4
n+5
n+6
n+7
n+8 Loop 1
n+9 Loop 2
Data item
Bit
15 to 00
Loop 1 PV
15 to 00
Loop 2 PV
15 to 00
Loop 1 SP
15 to 00
Loop 2 SP
15 to 12
Loop 1
executed
bank
number
11 to 08
Loop 2
executed
bank
number
07 to 02
---
01
SW2-2
00
SW2-1
15
---
14
Sensor
error
13
CT
overflow
12 to 09
---
08
RUN
07 and 06
---
05
Cooling
control
output
04
Heating
control
output
03
AT
02
HB
01
AL1
00
AL2
Note If the setting direction of the Temperature Control Unit is set to the C200H PC
and the C200H is in program mode, all word data will be 0. Therefore, if the
C200H in program mode has been set to continuous control, the Temperature
Control Unit executes temperature control when the C200H stops operating,
judging that the SP has been changed to 0 C. To prevent this, set SW2-2 of the
Temperature Control Unit to OFF (i.e., the setting direction is set to the Data Set-
ting Console) before the C200H stops operating and reset SW2-2 after the
C200H restarts.
Data contents
Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit
BCD data For platinum resistance thermometer data the least
BCD data. For platinum resistance thermometer data, the least
significant digit is 0.1. The most significant digit is F for minus (–).
Outputs the Loop 1 and Loop 2 SP (set point) as 4-digit BCD
data. For platinum resistance thermometer data, the least
data For platinum resistance thermometer data the least
significant digit is 0.1. The most significant digit is F for minus (–).
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
Not used. Set to 0.
Bit set to 1 if the sensor is not connected, a sensor
wire is broken, or the input data exceeds the
operational temperature range.
Bit set to 1 when the detected heater current
exceeds 55.0 A.
Not used. Each bit is set to 0.
Bit set to 1 during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or
voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Bit set to 1 if the detected heater current drops
below the set heater burnout current value. (HB:
heater burnout)
Bit set to 1 when the temperature enters the set
alarm range (Refer to page 23).
l
(R f
t
Section 4-1
23)
Loop 1/2
status data
39