Operating Procedure

3-1

Operating Procedure

1, 2, 3...
20
After preparing the C200H PC, follow the procedure below to use the Heat/Cool
Temperature Control Unit.
1. Set the switches on the front and rear panels according to the operating con-
ditions. (Refer to 2-2 Switch Settings. )
Set SW2-2 under the display cover to the OFF position to enable data set-
ting from the Data Setting Console.
2. Mount to Rack.
Turn off the C200H power supply before mounting or dismounting the
C200H on the Rack.
3. Connect the input wiring. (Refer to 2-3 Wiring. )
The 24-VDC power supply must be connected. The Data Setting Console
will not operate unless the 24-VDC power supply is connected. The sensors
can be connected immediately before the system is tested.
4. Connect the Data Setting Console. (Refer to 2-3-3 Data Setting Console
Cables .)
5. Turn on the 24-VDC and the C200H power supplies.
Set the C200H to PROGRAM mode.
6. Use the Data Setting Console to make the settings for the parameters that
need to be changed. (Refer to the rest of this section.)
7. Test operation and adjust data. (Refer to the rest of this section.)
Connect the output wiring and turn on the heater power. To start the test op-
eration, turn ON the RUN bit of the loop that is to be controlled with a device
such as the Programming Console. Monitor the control conditions and ad-
just the data until the required control is achieved. During operation, the
"bank no." is switched to "executed bank no." and cannot be changed from
the Data Setting Console. To change it, use a device such as the Program-
ming Console, or use the user program.
8. Create the user programs. (Refer to Section 4 PC Memory Allocation and
Programming. )
Arrange the data for the test operation, and create the user programs for
data setting, monitoring, switching the bank number, and so on. Set SW2-2
under the display cover to the ON position to enable data setting from the
C200H PC.
9. Start operation.
Section 3-1