Electrodes Setting - PSG 15 Kw Installation And Operating Instructions Manual

Wood and combined 15 kw, 18 kw, 20 kw, 25 kw and uh-caddy
Table of Contents

Advertisement

COMBUSTION VERIFICATION PROCEDURE:
A- DRILL A 9/32" DIAMETER HOLE IN THE EVACUATION PIPE APPROXIMATELY 18" FROM THE
OUTLET.
B- CLOSE THE DOOR AND THE AIR INTAKE(S) OF THE WOOD BURNING FURNACE.
C- LIGHT THE BURNER FOR AT LEAST 10 TO 15 MINUTES.
D- OVER THE FIRE DRAUCHT = -0.01 TO -0.02 W.C. (THE DRAFT OVER THE FIRE MUST BE
MEASURED IN THE OPENING IN THE PULSATION TRAP).
E- SMOKE TEST BETWEEN 0 AND 1 ON THE SHELL BACHARACH SCALE (TRACES).
F- DRAFT IN THE CHIMNEY =-0.02 TO -0.04 W.C.
G- PERCENTAGE OF EXCESS AIR = 20 TO 40%, 12% CO2, 4.6% O
H- AVERAGE EFFICIENCY OF 80 TO 85 %.
I- TIGHTEN ALL THE LOCKING SCREWS AFTER COMPLETING THE FINAL ADJUSTMENT.
N.B. – The barometric damper provided with the appliance must be properly installed on the flue pipe of the
oil burning unit. The purpose of the damper is to adjust the draft in the evacuation pipe of the oil
burning unit to the recommended level. Since the evacuation pipe of the oil burning unit is connected
on the evacuation pipe of the wood burning furnace, the minimum draft to be respected is 0.04"
W.C. in the evacuation pipe of the wood burning side, at all time. In fact, a barometric damper
that would be opened too wide could cause an important loss of draft in the evacuation pipe
of the wood burning furnace.

ELECTRODES SETTING

The electrodes must be adjusted by a qualified technician. A proper positioning of the electrodes is
important to get an efficient lighting of the oil.
ELECTRODE SETTING FOR "F" HEAD
5/32"
7/16"
ELECTRODE
1/16"
31
.
2
NOZZLE

Advertisement

Table of Contents
loading

This manual is also suitable for:

18 kw20 kw25 kwUh-caddyCaddy series

Table of Contents