Description Of Terminal Functions - Centsys VECTOR2 Installation Manual

Linear swing gate operator
Table of Contents

Advertisement

24. Description of terminal functions

S Sens1
Motor S (MTR S) operator. Connects to the thin PURPLE wire of the Motor
S operator.
S Sens2
Motor S (MTR S) operator. Connects to the thin BLUE or ORANGE wire of
the Motor S operator.
M Sens1
Motor M (MTR M) operator. Connects to the thin PURPLE wire of the Motor
M operator.
M Sens2
Motor M (MTR M) operator. Connects to the thin BLUE or ORANGE wire of
the Motor M operator.
Sens +
Operator sensor power connection. A 5V output for connecting to the thin
RED sensor wireon both the MTR M and MTR S operators.
Sens -
Operator sensor power connection. A 0V output for connecting to the thin
BLACK or GREY sensor wire on both the MTR M and MTR S operators.
Safe CLS
CLOSING edge safety input. (A normally-closed potential-free input).
For as long as a connection between this input and COM is maintained the
controller will behave normally. When this connection is broken it will
prevent the gate from closing if it is stationary, and will stop and reverse
the gate if it is closing. This input has no effect if the gate is opening.
normally.*)
Safe OPN
OPENING edge safety input. (A normally-closed potential-free input).
For as long as a connection between this input and COM is maintained the
controller will behave normally. When this connection is broken it will
prevent the gate from opening if it is stationary, and will stop and reverse
the gate if it is opening. This input has no effect if the gate is closing.
LCK/STP
Holiday Lockout or gate STOP input. (A normally-closed potential-free
input). For as long as a connection between this input and COM is
maintained the controller will behave normally. But, when this connection
to COM is broken all inputs are inhibited, and if the gate is moving it will
stop.
(If the Saf CLS function is not required a link must be fitted
between Safe CLS and COM for the controller to operate
(If the Safe OPEN and reverse functions are not required a link
must be fitted between safe OPEN and COM for the controller to
operate normally. )
When setting up the controller for the first time or after a full
reset back to factory default has been performed, the system will
electronically override the Safety Inputs and allow the system to
function without the links. However if safeties are connected to
either or both inputs, thereafter there must be a normally closed
circuit maintained for the system to operate correctly. I.e. if
beams are fitted and then removed, the circuit which is affected
must be replaced with a wire link to create the normally closed
circuit
(If the LCK function is not required a link must be fitted between
LCK and COM.)
Page 58