Ramp-up distance
Sets the ramp-up distance in millimeters of travel of the piston when starting.
This setting applies to both motors
Ramp-down distance
Sets the ramp-down distance in millimeters of travel of the piston when
stopping. This setting applies to both motors.
Crawl distance
Sets the final crawl distance in millimeters of travel of the piston when
reaching an endpoint. This setting applies to both motors.
Push force limit
Sets the maximum push force delivered by the motors. The maximum setting
is a value of 15 and the minimum is four. This is useful in cases where limited
push force is required. This setting applies to both motors.
Menu 6 - IR beams
In a swing gate installation, in order to
provide protection for a person or
vehicle moving through the entrance,
it is necessary to have two sets of
beams, one across the driveway where
the gates are closed and another
where the gates are open. Both these
beams must be set as closing safety
beams, preventing the gate from
closing and stop the gates if they have
started to close.
However, across the line of the
driveway up to where the gates open,
it is also recommended to have
another set of safety beams to prevent
the gate from opening if they are
closed and stop if they are opening.
Two independent normally-closed
inputs are provided for opening and
closing safety beams.
An interrupted closing beam will prevent the gates from closing and stop and
reverse the gates back to the open position if already opening. Vice- versa for a
closing beam.
FIGURE 67. TYPICAL CLOSING BEAM
Page 49
Outside
closing beam
Gates will not close
Inside
closing beam
INSTALLATION