Ip Query - ABB SPA-ZC 400 Installation And Commissioning Manual

Ethernet adapter modbus/tcp brigde
Table of Contents

Advertisement

1MRS756014
8.3.
Ethernet Adapter
Modbus/TCP Brigde
Installation and Commissioning Manual
Only one SPA client can be configured to poll SPA events from
the device. By default SPA-ZC 400 is configured to poll SPA
events. In this case, it is not allowed to poll SPA events from
another SPA client.
SPA command timeout in IED
*
SPA command timeout should be < 1 second when LON interlocking is not in
use.
SPA baud rate and SPA slave number in IED
*
Baud rate and slave number have to be according to the SPA-ZC 400
configuration in X3.2/Communication 2.

IP Query

By using the IP Query Tool in Communication Engineering Tool (CET) for
SPA-ZC 40x, it is possible to see all connected SPA-ZC 40x, devices, their
communication parameters and version information.
Example:
S e n d i n g I P q u e r y 1
R E C E I V E D M E S S A G E F R O M 1 0 . 5 8 . 1 2 5 . 1 5 1 :
M a c A d d r e s s : 0 0 - 0 C - 0 2 - B 0 - 0 4 - 8 9
S u b n e t M a s k : 2 5 5 . 2 5 5 . 2 5 5 . 0
D e f a u l t G a t e w a y : 1 0 . 5 8 . 1 2 5 . 1 5 0
S N T P s e r v e r s : 1 0 . 5 8 . 1 2 5 . 1 5 0
S W _ S P A T Y P E : S P A - Z C 4 0 x
S W _ N U M B E R : 1 M R S 1 1 8 5 3 3
S W _ B U I L D : 1 1 0
S W _ R E V I S I O N : B
C o m p i l e r D A T E _ T I M E : N o v 2 8 2 0 0 5 1 2 : 3 8 : 0 2
To use the IP Query Tool:
1. Select Tools > IP Query Tool to start the tool, see Fig. 8.3.-1.
Query activates devices from the network until it is stopped.
Fig. 8.3.-1
Starting the IP Query Tool
2. Select the Network adapter to send a query, see Fig. 8.3.-2.
SPA-ZC 400
1 2 7 . 0 . 0 . 1
A060127
43