Blade Server Error Messages - IBM BladeCenter T Hardware Maintenance Manual And Troubleshooting Manual

Type 8267
Hide thumbs Also See for BladeCenter T:
Table of Contents

Advertisement

Note: See Chapter 7, "Parts listing, BladeCenter T Type 8267," on page 101 to determine which components should
be replaced by a field service technician.
Message
System over recommended voltage for
+12V
System over recommended voltage for
+1.8V
System over recommended voltage for
+2.5V
System over recommended voltage for
+3.3V
System over recommended voltage for 5V 1. Reseat the management module.
System over recommended voltage for
+5V
System under recommended voltage for
+12V
System under recommended voltage for
+1.8V
System under recommended voltage for
+2.5V
System under recommended voltage for
3.3V
System under recommended voltage for
5V
System is under recommended voltage for
+5V
System running nonredundant power

Blade server error messages

Note: See Chapter 7, "Parts listing, BladeCenter T Type 8267," on page 101 to determine which components should
be replaced by a field service technician.
Message
Blade server x was installed.
Blade server x was removed.
Received an [xxx] alert from an
unsupported ISMP type xxxx, via the
interconnect network.
Action
1. Reseat the management module.
2. Reseat the power modules.
3. Replace the power modules.
4. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
1. Reseat the management module.
2. Replace the management module.
Make sure that power modules 1 and 2 are installed and operating
correctly. If blade servers are installed in bay 5 or higher, make sure
that power modules 3 and 4 are installed and working correctly.
Action
Information only. Take action as required.
Information only. Take action as required.
Ensure that all blade servers in the blade center are supported by the
management module.
Chapter 6. Symptom-to-FRU index
95