(2) Warnings
When a warning occurs, the output is not shut off.
Operation panel
OL
indication
Name
Stall prevention (overcurrent)
During
acceleration
During
constant-
Description
speed
operation
During
deceleration
1. Check that the Pr. 0 Torque boost setting is not too large.
2. Check that the Pr. 7 Acceleration time and Pr. 8 Deceleration time settings are not too small.
3. Check that the load is not too heavy.
Check point
4. Are there any failure in peripheral devices?
5. Check that the Pr. 13 Starting frequency is not too large.
6. Check that the Pr. 22 Stall prevention operation level is appropriate
1. Increase or decrease the Pr. 0 Torque boost setting 1% by 1% and check the motor status. (Refer to page 69)
2. Set a larger value in Pr. 7 Acceleration time and Pr. 8 Deceleration time. (Refer to page 91)
3. Reduce the load weight.
4. Try general-purpose magnetic flux vector control.
Corrective action
5. Change the Pr. 14 Load pattern selection setting.
6. Set stall prevention operation current in Pr. 22 Stall prevention operation level. (The initial value is 150%.) The
acceleration/deceleration time may change. Increase the stall prevention operation level with Pr. 22 Stall prevention
operation level, or disable stall prevention with Pr. 156 Stall prevention operation selection. (Operation at OL
occurrence can be selected using Pr. 156.)
Operation panel
oL
indication
Name
Stall prevention (overvoltage)
During
Description
deceleration
Check for sudden speed reduction.
Check point
Check that regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886) is used. (Refer to page 223).
Corrective action
The deceleration time may change. Increase the deceleration time using Pr. 8 Deceleration time.
FR-PU04
FR-PU07
When the output current of the inverter exceeds the stall prevention operation level (Pr. 22 Stall
prevention operation level, etc.), this function stops the increase in frequency until the overload current
decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has
reduced below stall prevention operation level, this function increases the frequency again.
When the output current of the inverter exceeds the stall prevention operation level (Pr. 22 Stall
prevention operation level, etc.), this function reduces frequency until the overload current decreases to
prevent the inverter from resulting in overcurrent trip. When the overload current has reduced below
stall prevention operation level, this function increases the frequency up to the set value.
When the output current of the inverter exceeds the stall prevention operation level (Pr. 22 Stall
prevention operation level, etc.), this function stops the decrease in frequency until the overload current
decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has
decreased below stall prevention operation level, this function decreases the frequency again.
FR-PU04
FR-PU07
If the regenerative energy of the motor becomes excessive to exceed the regenerative energy
consumption capability, this function stops the decrease in frequency to prevent overvoltage trip.
As soon as the regenerative energy has reduced, deceleration resumes.
If the regenerative energy of the motor becomes excessive when regeneration avoidance function
is selected (Pr. 882 =1), this function increases the speed to prevent overvoltage trip.
(Refer to page 223).
Causes and corrective actions
OL
oL
5
247