Mitsubishi Electric FR-D700 Instruction Manual page 134

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

Monitor display and monitor output signal
(2) How to calibrate the terminal AM when using the operation panel
Operation
1.
Confirmation of the RUN indication and
operation mode indication
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Turn
until
5.
Turn
until
Set to C1 AM terminal calibration.
6.
Press
to enable setting.
7.
If the inverter is at a stop, press the
to start the inverter.
(Motor needs not be connected.)
8.
Turn
to adjust the indicator needle to the
desired position.
9.
Press
.
Setting is complete.
Turn
Press
Press
REMARKS
Calibration can also be made for external operation. Set the frequency in the external operation mode, and make calibration in
the above procedure.
Calibration can be made even during operation.
For operation from the parameter unit (FR-PU04/FR-PU07), refer to the instruction manual of the parameter unit.
Parameters referred to
Pr. 55 Frequency monitoring reference
Pr. 56 Current monitoring reference
Pr. 158 AM terminal function selection
130
appears.
appears.
appears.
key
to read another parameter.
to return to the
indication (step 4).
twice to show the next parameter (
Refer to page 128
Refer to page 128
Refer to page 123
(When Pr. 158 = 1)
PRM indication is lit.
(The parameter number read previously appears.)
C1 to C7 setting
is enabled.
Analog indicator
Flicker...Parameter setting complete!!
).
Display
The monitor set to Pr. 158
AM terminal function selection
is displayed.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents