4.10.4 Start signal operation selection (STF, STR, STOP signal, Pr. 250)

You can select the operation of the start signal (STF/STR).
Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off.
Used to stop the motor with a mechanical brake, etc. together with switching off of the start signal.
(Refer to page 107 for stop selection)
Parameter
Name
Number
Stop
250
selection
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 157)
(1) Two-wire type connection (STF, STR signal)
The two-wire connection is shown below.
In the default setting, the forward/reverse rotation signals (STF/STR) are used as start and stop signals. Turn on either of
the forward and reverse rotation signals to start the motor in the corresponding direction. Switch on both or switch off (or
both on) the start signal during operation to decelerate the inverter to a stop.
The speed setting signal may either be given by entering 0 to 10VDC across the speed setting input terminal 2-5, by
setting the required values in Pr. 4 to Pr. 6 Multi-speed setting (high, middle, low speeds), etc.
(For multi-speed operation, refer to page 84.)
When Pr. 250 is set to any of "1000 to 1100, 8888", the STF signal becomes a start command and the STR signal a
forward/reverse command.
Forward rotation start
Reverse rotation start
Forward
rotation
Reverse
rotation
ON
STF
STR
2-wire connection example (Pr. 250 = "9999")
REMARKS
When Pr. 250 is set to any of "0 to 100, 1000 to 1100", turning off the start command coasts the inverter to a stop. (Refer to page 107)
The STF and STR signals are assigned to the STF and STR terminals in the default setting. The STF signal can be assigned to
Pr. 178 STF terminal function selection, and the STR signal to Pr. 179 STR terminal function selection only.
112
Initial
Setting Range
Value
0 to 100s
1000s to 1100s
9999
9999
8888
STF
Inverter
STR
PC
10
2
5
Time
ON
Start signal
(STF/STR)
STF signal: Forward rotation start
STR signal: Reverse rotation start
STF signal: Start signal
STR signal: Forward/reverse signal
STF signal: Forward rotation start
STR signal: Reverse rotation start
STF signal: Start signal
STR signal: Forward/reverse signal
Start signal
Forward/reverse
signal
Forward
rotation
Reverse
rotation
ON
STF
STR
2-wire connection example (Pr. 250 = "8888")
Description
Stop operation
Refer to page 107
The motor is coasted to a stop
when the preset time elapses
after the start signal is turned off.
When the setting is any of 1000s to
1100s, the inverter coasts to a stop
in (Pr. 250 - 1000)s.
When the start signal is turned
off, the motor decelerates to
stop.
STF
Inverter
STR
PC
10
2
5
ON
Time