Inverter Placement - Mitsubishi Electric FR-D700 Instruction Manual

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

Installation of the inverter and enclosure design
1.4.3

Inverter placement

(1) Installation of the inverter
Enclosure surface mounting
FR-D740-012 or more
FR-D720S-070 and 100
Remove the front cover and
wiring cover to fix the inverter to
the surface.
Front cover
NOTE
When encasing multiple brake units, install them in parallel as a
cooling measure.
Install the inverter vertically.
(2) Clearances around inverter
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
Surrounding air temperature and humidity
5cm
Inverter
Measurement
position
Temperature: -10 C to +50 C
Humidity: 90% RH maximum
Leave enough clearances and
take cooling measures.
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
(4) Above inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be
heat resistant.
10
Wiring cover
Clearances (front)
Measurement
position
5cm
1cm
or more*
5cm
* When using the inverters at the surrounding
air temperature of 40 C or less, the inverters
can be installed without any clearance
between them (0cm clearance).
When surrounding air temperature exceeds
40 C, clearances between the inverters
should be 1cm or more (5cm or more for the
FR-D740-120 or more).
FR-D720S-008 to 042
Front cover
Clearances (side)
10cm or more
1cm
or more*
10cm or more
* 5cm or more for the FR-
D740-120 or more
Wiring cover
Inverter
1cm
or more
*