Mitsubishi Electric FR-D700 Instruction Manual page 217

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

(8)
Adjustment procedure
Parameter setting
Terminal setting
Turn on the X14 signal.
Operation
(9)
Calibration example
(A detector of 4mA at 0°C and 20mA at 50°C is used to adjust the room temperature to 25°C under PID control.
The set point is given to across inverter terminals 2-5 (0 to 5V).)
Start
Determination of set point
Determine the set point of
what is desired to be adjusted.
Conversion of set point into %
Calculate the ratio of the set
point to the detector output.
Make calibration.
Setting of set point
Input a voltage across terminals
2-5 according to the set value %.
Operation
Set the proportional band (Pr.
129 ) to a slightly larger value,
the integral time (Pr. 130 ) to a
slightly longer time, and the
differential time (Pr. 134 ) to
"9999" (no function), and turn
on the start signal.
Is the set point stable?
No
Parameter adjustment
To stabilize the measured value,
change the proportional band (Pr.
129 ) to a larger value, the integral
time (Pr. 130 ) to a slightly longer
time, and the differential time (Pr.
134 ) to a slightly shorter time.
Adjustment end
*
Adjust the PID control parameters, Pr. 127 to Pr. 134.
Set the I/O terminals for PID control (Pr. 178 to Pr. 182 (input terminal
function selection), Pr. 190 , Pr. 192 (output terminal function selection))
When X14 signal is not assigned, setting a value other than "0" in Pr.
128 activates PID operation.
Set the room temperature to 25 C.
Set Pr. 128 and turn on the X14 signal to enable PID control.
Detector specifications
When 0
4mA and 50
the assumption that 4mA is 0% and 20mA is 100%.
Make the following calibration* when the target setting input (0 to 5V) and
detector output (4 to 20mA) must be calibrated.
When the set point is 50%
As the terminal 2 specifications are 0%
to the terminal 2 for the set point of 50%.
When the parameter unit is used for operation, input the set point (0 to
100%) in Pr. 133.
When performing operation, first set the proportional band (Pr. 129 ) to a
slightly larger value, the integral time (Pr. 130 ) to a slightly longer time,
and the differential time (Pr. 134 ) to "9999" (no function), and while looking
at the system operation, decrease the proportional band (Pr. 129 ) and
increase the integral time (Pr. 130 ).
Yes
Parameter optimization
While the measured value is stable
throughout the operation status, the
proportional band (Pr. 129 ) may be
decreased, the integral time (Pr. 130 )
decreased, and the differential time
(Pr. 134 ) increased.
Using calibration Pr. 902 and Pr. 903 (terminal 2) or Pr. 904 and Pr. 905 (terminal
When calibration
is required
4), calibrate the detector output and target setting input.
Make calibration in the PU mode during an inverter stop.
Special operation and frequency control
20mA are used, the set point 25
0V and 100%
is 50% on
5V, input 2.5V
213
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents