Stop operation selection at occurrence of communication fault (Pr. 502)
Stop operation when retry count excess (Mitsubishi inverter protocol only) or signal loss detection error occurs can be selected.
Operation at fault occurrence
Pr. 502 Setting
0 (initial value)
1
2
Operation at fault removal
Pr.502 Setting
0 (initial value)
1
2
Automatic restart functions
Pr. 502 setting "0" (initial value)
Fault occurrence
Communication
OFF
fault
Fault display
(E.PUE)
Fault output
OFF
(ALM)
Pr. 502 setting "2"
Fault occurrence
Communication
OFF
fault
Fault display
(E.PUE)
Fault output
OFF
(ALM)
REMARKS
The fault output indicates fault output signal (ALM signal) or alarm bit output.
When the setting was made to provide a fault output, the fault description is stored into the faults history. (The fault description
is written to the faults history when a fault output is provided.)
When no fault output is provided, the fault definition overwrites the fault indication of the faults history temporarily, but is not
stored.
After the fault is removed, the fault indication returns to the ordinary monitor, and the faults history returns to the preceding fault
indication.
When the Pr. 502 setting is "1 or 2", the deceleration time is the ordinary deceleration time setting (e.g. Pr. 8, Pr. 44, Pr. 45). In
addition, acceleration time for restart is the normal acceleration time (e.g. Pr. 7, Pr. 44).
When "2" is set in Pr. 502, run command/speed command at restarting follows the command before an fault occurrence.
When "2" is set in Pr. 502 at occurrence of a communication error and the error is removed during deceleration, the inverter
accelerates again at that point.
Parameters referred to
Pr. 7 Acceleration time, Pr. 8 Deceleration time
Pr. 190, Pr. 192 (output terminal function selection)
Operation
Coasts to stop.
Decelerates to stop
E. PUE lit after stop
Operation
Kept stopped
Fault removal
ON
OFF
Motor coasting
Display
ON
Fault removal
ON
OFF
Decelerates
to stop
Display
Refer to page 91
Refer to page 114
Communication operation and setting
Indication
Fault Output
E. PUE lit
Provided
Provided after stop
Not provided
Indication
Fault Output
E. PUE
Kept provided
Normal display
Not provided
Pr. 502 setting "1"
Communication
OFF
fault
Time
Fault display
(E.PUE)
Fault output
(ALM)
Time
Fault occurrence
Fault removal
ON
Decelerates to stop
Display
OFF
ON
OFF
Time
4
181