Peripheral Devices - Mitsubishi Electric FR-D700 Instruction Manual

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

Inverter and peripheral devices
1.2.1

Peripheral devices

Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity.
Refer to the following list and prepare appropriate peripheral devices:
Inverter Type
FR-D740-012
FR-D740-022
FR-D740-036
FR-D740-050
FR-D740-080
FR-D740-120
FR-D740-160
FR-D720S-008
FR-D720S-014
FR-D720S-025
FR-D720S-042
FR-D720S-070
FR-D720S-100
∗1
Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
∗2
For installations in the United States or Canada, use the class T type fuse certified by the UL and cUL.
∗3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the inverter type
and cable and reactor according to the motor output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter,
etc. Identify the cause of the trip, then remove the cause and power on the breaker.
4
Moulded Case Circuit Breaker (MCCB) ∗1
Motor
or Earth Leakage Circuit Breaker (ELB) ∗2
Output
(kW)
without
0.4
30AF 5A
0.75
30AF 5A
1.5
30AF 10A
2.2
30AF 15A
3.7
30AF 20A
5.5
30AF 30A
7.5
30AF 30A
0.1
30AF 5A
0.2
30AF 5A
0.4
30AF 10A
0.75
30AF 15A
1.5
30AF 30A
2.2
30AF 40A
Reactor connection
with
30AF 5A
30AF 5A
30AF 10A
30AF 10A
30AF 15A
30AF 20A
30AF 30A
30AF 5A
30AF 5A
30AF 5A
30AF 10A
30AF 15A
30AF 30A
Magnetic Contactor (MC) ∗3
Reactor connection
without
with
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20
S-N11, S-N12
S-N20
S-N20
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20, S-N21
S-N10
MCCB
INV
MCCB
INV
IM
IM