4.18.3 Start command source and frequency command source during communication
operation (Pr. 338, Pr. 339, Pr. 551)
When the RS-485 communication with the PU connector is used, the external start command and frequency command
can be made valid. Command source in the PU operation mode can be selected.
From the communication device, parameter unit, etc. which have command source, parameter write or start command
can be executed. Parameter read or monitoring can be executed in any operation mode.
Parameter
Name
Number
Communication operation
338
command source
Communication speed
339
command source
PU mode operation
551 ∗
command source
selection
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 157)
* Pr. 551 is always write-enabled.
(1)
Selects the command source of the PU operation mode (Pr. 551)
Any of the operation panel, PU connector can be specified as the command source in the PU operation mode.
In the PU operation mode, set Pr. 551 to "2" when executing parameter write, start command or frequency command
during the RS-485 communication with PU communication.
PU...PU operation mode, NET...network operation mode, —....without command source
Pr. 551
Setting
2
4
9999
(initial value)
∗1
The Modbus-RTU protocol cannot be used in the PU operation mode. When using the Modbus-RTU protocol, set Pr. 551 ≠ "2".
∗2
When Pr. 551 = "9999", the priorities of the PU control source is parameter unit (FR-PU04/FR-PU07) > operation panel.
NOTE
When performing the RS-485 communication with the PU connector when Pr. 551 = "9999", PU mode command
source does not automatically change to the PU connector.
When Pr. 551 = "2" (PU mode PU connector), the operation mode cannot be switched to the network operation mode.
Changed setting value is made valid when powering on or resetting the inverter.
The Modbus-RTU protocol cannot be used in the PU operation mode. Select network operation mode (NET mode
command source).
Selection of operation mode and operation location
Initial
Setting
Value
Range
0
0
9999
9999
Command Source
Operation
Parameter
panel
unit
PU
PU
PU ∗2
PU ∗2
0
Start command source communication
1
Start command source external
0
Frequency command source communication
Frequency command source external (Frequency command from
1
communication is invalid, frequency command from terminal 2 is
valid)
Frequency command source external (Frequency command from
2
communication is valid, frequency command from terminal 2 is
invalid)
2
PU connector is the command source when PU operation mode.
4
Operation panel is the command source when PU operation mode.
Parameter unit automatic recognition
Normally, operation panel is the command source. When the
parameter unit is connected to the PU connector, PU is the
command source.
RS-485
communication
Switching to NET operation mode
PU ∗1
disabled
NET
NET
Description
Remarks
4
171